Installing the Configuration
Software
Refer to Table 5 for the equipment needed.
1. Insert the
Moore Industries Interface Solution
PC Configuration Software
CD into the CD
drive of the PC. Access the CD and open
the
SDY SIY TDY TRX TRY 64 bit PC
Configuration software
folder.
2. Double-click the installation program located
in the folder. Follow the prompts to correctly
install the program.
Once the Configuration Program is installed on the
PC, the TDY can be connected to equipment to
simulate input and monitor output. You can then
change the transmitter’s operating parameter
Gathering the Equipment Needed
It is possible to create a Configuration File for a TDY
without ever connecting the transmitter to a PC.
Most TDY operating parameters can be setup, saved
in a Configuration File, and stored on disk entirely
within the Configuration Program—without ever
communicating with a transmitter.
It is not possible to trim the transmitter input or
output without a transmitter, a source of input,
and a meter (for output trimming). Likewise, it is
not possible to use the Loop Test function of the
transmitter unless everything is setup as shown in
Figure 2, and it is not possible to store a tag name in
the memory of a transmitter without connecting that
transmitter to the Configuration Program.
Table 3 lists the things needed to setup the TDY as
shown in Figure 2.
Device
Specifications
Note:
Be sure to use calibrated test equipment when
performing any trimming operations on the TDY.
Moore Industries uses equipment rated 5:1 over the
rated accuracy of the unit under test.
We recommend the use of equipment
rated at least 3:1.
Table 3.
Equipment Needed for Setting Up the TDY
Thermocouple, RTD, Millivolt,
Potentiometer Simulator, or
Decade Resistance Box
Power Supply
Precision Load Resistor (Optional)
Multimeter
Thermocouple or RTD
Temperature vs. Resistance Tables
Personal Computer
Moore Industries’
TRX/TRY/ TDY/SIY/SDY
Configuration Software
Moore Industries’
Communication Cable
Accurate to ±0.05% of unit span
10-42Vdc, ±0.01%
250 ohms ±0.01%
Accurate to ±0.025%,
e.g. Fluke Model 87
ITS68 and ITS90, or equivalent
Microsoft Windows based PC;
16Mb free RAM; 20MB free
disk space on hard drive
Microsoft Windows XP, 7 or 10
and 1 (one) serial port
or one available USB port
Version 4.0 or greater, success
-
fully installed on the hard disk of the
specificied PC
Non- isolating (PN 803-040-26)
Isolating (PN 803-039-26)
USB Cable (PN 208-236-00)
Fuse protected USB Cable
(PN 804-030-26)