background image

TDY

 

Demand Moore Reliability 

19

Disabling Broken Wire Detection

One of the premier features of many of Moore 

 

Industries’ temperature transmitters is our Total 

Sensor Diagnostics

®

 system.  During operation, the 

TDY sends random micro-amp pulses through input 

wiring to check for broken wiring or a burned out 

sensor.

Working with a Millivolt Input

When the transmitter is connected to a PC, the “TDY 

Status” section of the Main Configuration screen 

 

displays the message “Broken Wire” whenever 

problems are detected on the input, and the 

transmitter itself drives its output upscale or 

downscale.

This can cause problems for some types of millivolt 

calibrators and input sources.  To permanently  

disable this feature when the TDY is working in a 

 

millivolt input configuration, set the “Broken Wire” 

radio button in the center-right section of the 

Configuration Screen to OFF.

 

 

Working with a Thermocouple or RTD Input

 

Total Sensor Diagnostics can also cause problems 

with some types of temperature calibrators.  It is not 

possible to disable the feature by setting the “Broken 

Wire” radio button to OFF, as with millivolt inputs.

Instead, when working with thermocouple or RTD 

 

inputs, set the “Calibration” radio button in the lower-

left area of the Configuration Screen to “Calibration 

Mode”.  This temporarily disables Total Sensor 

 

Diagnostics.

Note:

 

It is not possible to set a TDY transmitter into  

Calibration Mode (Sensor Diagnostics OFF) 

 

permanently.  The “Calibration Mode” setting remains 

in effect only until a Configuration File is downloaded 

to the transmitter.

Working with a Configuration File

Also, when working with a Configuration File, it may 

be necessary to turn off Total Sensor Diagnostics 

in order to complete the settings for one or another 

aspect of transmitter operation.  To do this, click on the 

“Stop BW” (Stop Broken Wire Detection) button when 

it is active on the bottom of the screen. 

Setting Miscellaneous Functions— 

Engineering Unit Readout, Input 

Filtering, Upscale or Downscale 

Drive, and Broken Wire Detection

There are several “radio buttons” on the TDY 

 

Configuration Program Main Screen that control 

 

ancillary transmitter functions.  It is not necessary to 

have a transmitter hooked up to the PC in order to set 

these parameters and save them in a Configuration 

File.

Setting Engineering Unit Readout

When a temperature sensor is designated as the input 

to the transmitter, the radio buttons for “Degree” are 

enabled.

Use this setting to have the Configuration Program 

calculate the Centigrade or Fahrenheit temperature for 

readout in the “Status” area of the screen whenever 

the PC is being used to monitor the input from the 

connected sensor and from the display if the  

“Input” option in the “Display” section is selected.

Setting Input Filtering

Use this radio button setting to filter out noise on the 

power to the transmitter.

Choosing Between  

Upscale and Downscale Drive

The TDY transmitter can be configured to provide a 

special warning, using its output, of a breakdown in 

its connected sensor or sensor wiring.  Use this radio 

button setting to configure the transmitter to drive its 

output either up to 24mA or down to 3.3mA when a 

sensor or sensor wiring failure is detected.

Note:

 

There is a difference between the available

 

Full Scale output setting and the Upscale Drive,

 

and between the available zero scale output setting 

and the Downscale Drive: 

 

The TDY transmitter will only output 24mA or 3.3mA 

(as configured) in the event of a sensor or sensor 

wiring failure (upscale/downscale drive).

 

If sensor input drops below the rated range, output 

drops to a minimum of 3.8mA.  If sensor input rises 

above the rated range, output rises to 21.4mA.

 

This allows the user to distinguish between an input 

failure and an input over or under-range condition.

Содержание TDY

Страница 1: ...a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual TDY PC Programmable Temperature Transmitter with Display No 235 740 00J M...

Страница 2: ...Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...re 10 Gathering the Equipment Needed 10 11 PC Configuration Software Summary 12 Keeping What You ve Got Safe Using the Get Setup Function 13 Selecting Input Type Wiring etc 14 Scaling the Input also S...

Страница 4: ...Connected TDY 23 Installing and Connecting the TDY 24 Connecting the TDY in an Application 24 Recommended Ground Wiring Practices 24 CE Conformity 24 Dimensions 25 26 Installation in Hazardous Locatio...

Страница 5: ...by user designation inversely proportional to the input Available in your choice of explosion proof or NEMA 4X enclosures the TDY has certified protection in even the toughest environments Combine th...

Страница 6: ...isplay is always two decimal places Range 99999 to 99999 Minimum Display Span 1 00 Operating and Storage Range Transmitter 40 C to 85 C 40 F to 185 F Display 20 C to 65 C 4 F to 149 F Relative Humidit...

Страница 7: ...o 650 C 148 to 1202 F 200 to 630 C 328 to 1166 F 200 to 510 C 328 to 950 F 200 to 600 C 328 to 1112 F 200 to 630 C 328 to 1166 F 200 to 850 C 328 to 1562 F 80 to 320 C 112 to 608 F 50 to 250 C 58 to 4...

Страница 8: ...explosion proof enclosure with two inch entry ports and a glass cover BH2TG 2 Hub explosion proof enclosure with two inch entry ports and a glass cover BH2MG 2 Hub explosion proof enclosure with two M...

Страница 9: ...TDY Configuration Program on a PC Once the program is loaded and running nearly all of the operating parameters for the connected transmitter are shown on a single screen see Figure 3 This makes it ea...

Страница 10: ...verything is setup as shown in Figure 2 and it is not possible to store a tag name in the memory of a transmitter without connecting that transmitter to the Configuration Program Table 3 lists the thi...

Страница 11: ...Y COMM CABLE 803 040 26 FOR NON ISOLATED 803 039 26 FOR ISOLATED 804 030 26 FOR USB Thermocouple Millivolts Inputs 2 Wire RTD Direct Resistance Inputs 3 Wire RTD Direct Resistance Inputs 4 Wire RTD Di...

Страница 12: ...Software and will be used often The names and functions of the individual command buttons may change when you press a button 5 Output These scroll bars control the scaling and damping values of the T...

Страница 13: ...am Main Screen To save the Configuration File already resident in the transmitter s memory 1 Start the PC Configuration Program making sure that the TDY is connected as shown in Figure 2 2 Click on th...

Страница 14: ...tton at the bottom center of the screen then on the Prog button This transfers the settings from the software to the memory of the connected transmitter CAUTION Any time a connected TDY is programmed...

Страница 15: ...wnloaded Skip to Step 6 for instructions on getting the settings programmed into TDY nonvolatile memory 5 Select one of these options a Download the current settings into the connected transmitter s m...

Страница 16: ...ay Full The display zero and display full show what values will actually be displayed If the pull down menu in Figure 7 and the radio button on Figure 8 both have Input selected then Display Zero will...

Страница 17: ...Program Screen do not take effect in the unit until the Configuration File is downloaded Skip to Step 5 for instructions on getting the settings programmed into TDY nonvolatile memory 4 Choose from on...

Страница 18: ...it for it to capture the value 8 Click on the button labelled QuiInTrim then the Stop button and finally the Prog button to send the trim values to the transmitter Trimming the Output The TDY has a fu...

Страница 19: ...o this click on the Stop BW Stop Broken Wire Detection button when it is active on the bottom of the screen Setting Miscellaneous Functions Engineering Unit Readout Input Filtering Upscale or Downscal...

Страница 20: ...Main Screen or enter a value directly into the space provided The default damping value is 0 seconds The maximum allowable damping value is 5 056 seconds Using the Loop Test The TDY Loop Test feature...

Страница 21: ...l down menu to set Linearization ON Then click the CustTabl button in the lower left area of the Configuration Main Screen Figure 11 Linearization Must be set to ON to Create a Custom Table 3 Click on...

Страница 22: ...ests filling in the EGU Engineering Units then the number of points and finally the values in the table 9 When the table is complete click on the QuitTabl button and answer Yes on the pop up dialog bo...

Страница 23: ...e File button to bring up the File Management portion of the program 2 Use the Explorer like file display see Figure 13 to locate the file to be retrieved and click on the file to highlight it 3 Click...

Страница 24: ...output signals from Moore Industries productsshouldbewiredusingashielded twisted pair wiring technique Shields should be connected to an earth or safety ground For the best shielding the shield should...

Страница 25: ...Dimensions of the HP housing for the TDY unit 83 8 mm 3 30 in 118 1 mm 4 65 in 130 mm 5 12 in 111 8 mm 4 40 in 82 6 mm 3 25 in 63 5 mm 2 50 in C L Interior Diameter 81 3 mm 3 2 in 134 6 mm 5 30 in In...

Страница 26: ...TDY unit PS PS 1 2 3 4 SDY 16 203 MA 65mm 2 55 in GND 1 2 NPT 102mm 4 00 in 84mm 3 31 in 68mm 2 69 in 129mm 5 06 in 10mm 38 in 53mm 2 09 in 124mm 4 90 in 66mm 2 60 in 25mm 1 00 in 102mm 4 00 in 119mm...

Страница 27: ...lled as Division 2 equipment the TDY shall be mounted within a tool secured enclosure which meets the requirements of ANSI ISA 61010 1or C22 2 No 1010 1 and be capable of accepting the applicable wiri...

Страница 28: ...all be installed in an enclosure which maintains an ingress protection rating of at least IP20 The communications port shall be programmed through Moore Industries Cable Part No 804 030 26 as describe...

Страница 29: ...ale causes this message in the Output section of the Configuration Screen This condition is downloadable to the unit and causes transmitter output to rise proportionally in response to a drop on the i...

Страница 30: ...selves on their ability to provide timely accurate and practical answers to your process instrumentation questions Factory phone numbers are listed on the back cover of this manual If problems involve...

Страница 31: ...ng the intrinsically safe option It also in cludes guidelines for setting up zener barriers neces sary in these types of applications These diagrams must be used to augment the installa tion instructi...

Страница 32: ...TDY 32 Demand Moore Reliability...

Страница 33: ...TDY Demand Moore Reliability 33...

Страница 34: ...y and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: