Type n Applications – Zone 2
II 3 G Ex nA IIC
When installed as Category 3 equipment, the TDY
shall be mounted within a tool-secured enclosure
which meets the requirements of EN 60079-0 and EN
60079-15 and is capable of accepting the applicable
wiring methods specified in EN 60079-14. The
enclosure shall, at a minimum, meet the requirements
of IP54.
On installation, the TDY shall be provided with supply
transient protection external to the apparatus such
that the voltage at the supply terminals of the TDY
does not exceed 119V peak or 119Vdc.
The COM port shall not be used in Hazardous areas.
IECEx Installations
Intrinsically Safe Applications - Zone 0
Ex ia IIC
The TDY shall be installed in an enclosure which
maintains an ingress protection rating of at least IP20.
The communications port shall be programmed
through Moore Industries Cable, Part No.
804-030-26, as described on Control Drawing
100-100-54.
The Cable cannot be used in Hazardous Areas or in
ambient temperatures in excess of 75° C.
Type n Applications – Zone 2
Ex nA IIC
When installed as EPL Gc equipment, the TDY
shall be mounted within a tool-secured enclosure
which meets the requirements of IEC60079-0
and IEC60079-15 and be capable of accepting
the applicable wiring methods for the country of
origin. The enclosure shall, at a minimum, meet the
requirements of IP54.
On installation, the TDY shall be provided with supply
transient protection external to the apparatus such
that the voltage at the supply terminals of the TDY
does not exceed 119V peak or 119Vdc.
The COM port shall not be used in Hazardous areas.