Functional Safety Dual Input Smart HART® Temperature Transmitter
STZ
SECTION 3
European Union Installations (ATEX 2014/34/EU Directive)
II (1) G [Ex ia Ga] IIC
II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
When installed in non-hazardous locations:
The STZ shall be mounted within a tool-secured enclosure capable of accepting the applicable wiring
methods specified in EN 60079-14. The enclosure shall, at a minimum, meet the requirements of IP20.
When installed as Category 3 equipment and/or in Zone 2 locations
:
The STZ shall be mounted within a tool-secured enclosure which meets the requirements of EN 60079-0
and EN 60079-15 and is capable of accepting the applicable wiring methods specified in EN 60079-14.
The enclosure shall, at a minimum, meet the requirements of IP54.
The non-metallic parts incorporated in the STZ DIN mount housing may generate an ignition-capable
level of electrostatic charge. The STZ shall not be installed in a location where the external conditions are
conducive to the build-up of electrostatic charge on such surfaces. Additionally, the equipment shall only
be cleaned with a damp cloth.
The STZ shall be provided with supply transient protection external to the apparatus such that the
voltage at the supply terminals does not exceed 119Vac peak or 119Vdc
IECEx Installations
[Ex ia Ga] IIC
Ex nA [ia Ga] IIC T4 Gc
When installed in unclassified locations:
The STZ shall be mounted within a tool-secured enclosure capable of accepting the applicable wiring
methods specified in IEC 60079-14. The enclosure shall, at a minimum, meet the requirements of IP20.
When installed in Zone 2 locations
The STZ The STZ shall be mounted within a tool-secured enclosure which meets the requirements of
IEC 60079-0 and IEC 60079-15 and is capable of accepting the applicable wiring methods specified in
IEC 60079-14. The enclosure shall, at a minimum, meet the requirements of IP54.
The non-metallic parts incorporated in the STZ DIN mount housing may generate an ignition-ca-
pable level of electrostatic charge. The STZ shall not be installed in a location where the external
conditions are conducive to the build-up of electrostatic charge on such surfaces. Additionally, the
equipment shall only be cleaned with a damp cloth.
The STZ shall be provided with supply transient protection external to the apparatus such that the
voltage at the supply terminals does not exceed 119Vac peak or 119Vdc.