www.miinet.com
Moore Industries-International, Inc.
- 6 -
User’s Manual
238-760-00K
May 2019
Functional Safety Dual Input Smart HART® Temperature Transmitter
STZ
Quick Start Guide
STZ Quick Start Guide
The STZ is ready to install and is either set up with your specified configuration or the default
configuration below. If you need to change any parameters this can be done using a HART
handheld configurator or FDT/DTM application (see Sections 4 & 5)
After programming your transmitter, install the unit into your application using the connection
diagrams and terminal designation table located in this manual.
If you are using the STZ in a safety instrumented system, then you must read and follow the
safety section 7 in this user manual.
Default Configuration - Single Sensor Mode
Sensor 1:
4Wire RTD, Pt3850, 100Ohms, 0-100deg C
Broken Wire:
Enabled
Sensor 2
: Disabled, 0 seconds
Filter:
60Hz
Running Average Filter:
Disabled, Setting: 1
PV Damping:
Disabled, 0 seconds
Display Source:
Primary Variable (PV)
Decimal Places:
Auto
Output:
4-20mA
Under Range Min Value:
3.8mA
Over Range Max Value:
21.6mA
Sensor Fail Mode:
Low, 3.6mA
PV is= Sensor 1
SV is= RJC Temperature
TV is= Sensor 1
QV is= Sensor 1
Fault Tolerance Flags:
Allow measurement out of conformance range=On,
Allow Limited=Off, Allow Dropping=Off
Advanced Features:
Off
HART Mode:
Full Access