Functional Safety Dual Input Smart HART® Temperature Transmitter
STZ
SECTION 4
Input Capture
– Input Capture is used to match the device input and output zero and full scale
to a known value.
Adjust input sensor to 0% value to STZ and follow the screen instructions. This will set the
device’s output to known 4mA value. Adjust input sensor to 100% value to STZ and follow
the screen instructions. This will set the device’s output to a known 20mA value.
Variable Trim
– This menu allows you to view the following options Device Variable Trim,
Device Variable Trim Reset, and Display Device Variable Trim. Refer to Figure 4.15.
AO Trim–
Directs you to a sub-menu. Here you can select Reset Trim, Trim Zero or Trim Full.
AO Trim Reset–
Directs you to a sub-menu. Here you can select No or Yes.
Loop Test–
A loop test may be performed in order to check output performance and accuracy
and to trim other instruments in the loop. Your output will be a current value, in mA, equal
to the value you input. You can check the other current devices on the loop and calibrate
them to this signal.
Input Simulation –
Allows you Clear or Set a simulated Input.
S1 Corrosion Detection –
This captures the nominal resistance value of Sensor 1, then
allows setting 2 threshold resistances (warning and alarm) to identify when corrosion
occurs. This applies only to Thermocouples and 3W and 4W RTDs. See section 1 for
more information on Corrosion Detection.
S2 Corrosion Detection –
This captures the nominal resistance value of Sensor 2, then allows
setting 2 threshold resistances (warning and alarm) to identify when corrosion occurs.
This applies only to Thermocouples and 3W and 4W RTDs. See section 1 for more
information on Corrosion Detection.
Unlatch Range Alarm–
This allows you to select and reset an actively latched range alarm
(1-4) provided that the input has returned to a non-alarm level.
Note:
The
Unlatch RA*
menus are only visible if
Advance Settings
is Enabled.
Note:
After making all desired changes enter SEND to update the unit.