Functional Safety Dual Input Smart HART® Temperature Transmitter
STZ
SECTION 6
Device Variable Status (HART Command 9)
Each Device Variable has an associated status byte which provides information about the quality
of the data (See STZ Diagnostics for more information)
Maintenance
Moore Industries suggests a quick check for terminal tightness and general unit condition every
year. Always adhere to any site requirements for programmed maintenance. The calibration of
this instrument should be checked every year and re-calibrated only when necessary.
0-3
4-5
6-7
Bit
Description
Unused
Limit Status
00 Not Limited
01 High Limited
10 Low Limited
11 Constant
Process
00 Bad
01 Manual/Fixed
10 Poor Accuracy
11 Good
Table 6.6
Device Variable Status HART Command 9