SECTION 6
Status Messages
Status messages are displayed on the STZ HP or HART Handheld/FDT host whenever there are
events which affect the sensor measurements, configuration or the unit itself.
When one or more failure condition is detected all error messages will be displayed on the STZ
HP in a cyclic manner for a period of 2 seconds per message.
Similar information is also provided in the HART status registers.
RJC T
ERROR
Problem with the RJC (Reference Junction Compensation) Temperature Sensor
BADDQ (Var
Name)
The referenced item (Device, Dynamic or Output Variable) had bad data
quality.
Error related to the sensor or output should follow.
ERROR
SNSRn
Problem with Sensor n, specific error
Message should follow
WIREn
BROKE
ADC SAT
The input is too high for the selected input range
BAD RJC
Reference Junction Compensation could not be applied
NORM FAIL
The physical measurement could not be converted to temperature
ON BCKUP
A Backup device variable (BU1-2, or BU2-1) is mapped as PV, and the primary
sensor has failed
CAN'T BCKUP
A Backup device variable (BU1-2, or BU2-1) is mapped as PV, and the backup
sensor has failed
STZ HP Display Condition
There is a broken wire on the previously referenced sensor. If the specific
broken wire cannot be detected, the message will state 'Wires Broke'
If the sensor wire is not actually broken, then the unit has an internal short
and should be returned to the factory.
Table 6.1.
STZ
Display Errors- Sensor Data