13
MCP15-500.9
Figure 13.3 - Vent Terminals for Condensing Gas
Furnace Option (D-Cabinet)
(refer to
Instructions
Step 1)
(refer to Instructions Step 3)
(refer to Instructions Step 2)
Figure 13.1 - Vent Terminal for Condensing Gas
Furnace Option (B-Cabinet Unit)
(refer to Instructions Step 1)
(refer to Instructions Step 2)
Section C: Condensing B or C-Cabinet Furnaces
•
Review Table 12.1 to verify this is the correct section for
the unit and furnace type installed. If not, refer to the
proper section as indicated for the unit as configured.
•
For units that require vent extension kits, refer to Literature
#MCP15-574, “Installation Instructions, Extended Vent Kit,
Model MPR Gas Heat”, otherwise install the vent
terminal(s) as shown in Figures 13.1 through 13.2. Note
the following installation steps:
B-Cabinet Units Only (refer to Figure 13.1)
Step 1
: Insert short vent pipe into the vent pipe reducer.
Insert that assembly into the rubber coupling on
the power exhauster outlet. Tighten the clamp on
the flexible coupling to secure the vent pipe.
Step 2
: Insert the outer vent pipe with termination elbow
through the enclosure wall grommet and into the
vent pipe section installed in Step 1.
Step 3
: Verify that the bird screen is inserted in the
termination elbow and that the vent terminal elbow
is oriented to exhaust straight down.
GAS HEATING OPTION VENT TERMINALS AND COMBUSTION AIR HOODS
C-Cabinet Units Only (refer to Figure 13.2)
Step 1
: Insert small diameter outside vent pipe termination
through enclosure wall grommet and into the
flexible rubber coupling on the right side power
exhaust outlet. Tighten the clamp on the flexible
coupling to secure the vent pipe.
Step 2
: Insert large diameter inner vent pipe assembly into
the flexible rubber coupling on the left side power
exhaust outlet. Tighten the clamp on the flexible
coupling to secure the vent pipe.
Step 3
: Insert large diameter outside vent pipe termination
through enclosure wall grommet and into the
interlocking joint of the inner vent pipe assembly
from Step 2.
Step 4
: Verify that the bird screens are inserted in the
termination elbows and that the vent terminal
elbow is oriented to exhaust straight down.
•
Once complete, proceed to the “Condensate Drain and
Trap Installation” Section.
Figure 13.2 - Vent Terminal for Condensing Gas
Furnace Option (C-Cabinet)
Section D: Condensing D-Cabinet Furnaces
•
Review Table 12.1 to verify this is the correct section for
the unit and furnace type installed. If not, refer to the
proper section as indicated for the unit as configured.
•
For units that require vent extension kits, refer to Literature
#MCP15-574, “Installation Instructions, Extended Vent Kit,
Model MPR Gas Heat”, otherwise install the vent
terminal(s) as shown in Figure 13.3. Note the following
installation steps:
D-Cabinet Units Only (refer to Figure 13.3)
Step 1
: Insert the outer vent pipe with termination elbow
through the enclosure wall grommet on one side of
the unit and into the rubber coupling on the power
exhauster outlet. Tighten the clamp on the flexible
coupling to secure the vent pipe.
Step 2
: Verify that the bird screen is inserted in the
termination elbow and that the vent terminal elbow
is oriented to exhaust straight down.
Step 3
: Repeat Steps 1 and 2 for the heating section on
the opposite side of the unit.
•
This is the only D-Cabinet gas heat configuration that does
NOT have combustion air hoods to be field installed.
•
Once complete, proceed to the “Condensate Drain and
Trap Installation” Section.
Refer to instructions
for installation of
termination elbow
Содержание MPR Series