MCP15-500.9
TABLE OF CONTENTS / SI (METRIC) CONVERSION FACTORS / UNIT LOCATION
TABLE OF CONTENTS
Inspection on Arrival ................................................................. 1
Special Precautions .................................................................. 2
SI (Metric) Conversion Factors ................................................ 3
Special Design Requests ......................................................... 3
Storage Prior to Installation ...................................................... 3
Unit Location ............................................................................ 4
Installation ........................................................................... 4-16
Combustible Material and Service Clearances .............. 4-5
Roof Curb Installation........................................................ 6
General Rigging Instructions/Unit Installation ................. 6-7
Duct Installation ................................................................. 7
Condensate Drain Installation/Utility Connections ............ 8
Electrical Connections .................................................. 9-10
Gas Connections ........................................................ 10-11
Vent Terminals and Combustion Air Hoods ............... 12-14
Gas Heating Option Condensate Drains & Traps ........... 15
Hot Water Piping Connections ........................................ 16
Start-Up Procedure ........................................................... 18-33
General....................................................................... 18-19
Blower Adjustments .................................................... 19-21
Airflow Proving Switch and Dirty Filter Switch ................ 21
Variable Air Movement Applications ................................ 21
Checking Refrigerant Charge.......................................... 22
Gas Heating Option.................................................... 23-31
Energy Recovery Option (B and D-Cabinet units only) ......32-33
Unit Features/Options Location Drawings ......................... 34-39
Dimensions/Weights ......................................................... 40-50
B-Cabinet Size Unit without Energy Recovery. .......... 40-41
B-Cabinet Size Unit with Energy Recovery. ............... 42-43
C-Cabinet Size Unit.................................................... 44-45
D-Cabinet Size Unit without Energy Recovery .......... 46-47
D-Cabinet Size Unit with Energy Recovery ............... 48-49
Base Model Weights ....................................................... 50
Option and Accessory Pressure Drop Tables ................... 51-53
Maintenance ...................................................................... 54-57
Service & Troubleshooting ................................................ 58-61
Serial Plates ........................................................................... 62
Model Nomenclature ......................................................... 63-66
Commercial Warranty ................................................Back Page
SI (METRIC) CONVERSION FACTORS
Special Design Requests
Modine Manufacturing Company will sometimes build units
with special features as requested by the customer. This
manual only covers standard features and does not include any
changes made for special feature requests by the customer.
Units built with special features are noted with a 5-digit SPO
(Special Product Order) Number on the Serial Plate
Storage Prior to Installation
If the unit is stored outside prior to installation, the unit should
be covered to protect the inlet and duct openings from the
weather.
IMPORTANT
1. To prevent premature heat exchanger failure, do
not locate ANY gas-fired appliances in areas where
corrosive vapors (i.e. chlorinated, halogenated or acid)
are present in the atmosphere.
2. A properly designed drain with trap must be installed
immediately after the unit evaporator coil condensate
drain pan connection. Failure to do so will result in
condensate that cannot properly drain from the unit,
eventually causing the drain pan to fill. To prevent
damage to the building or unit, a drain pan float switch
is included as standard and will disable the unit if the
maximum condensate level is reached.
3. To prevent premature heat exchanger failure, the input
to the appliance, as indicated on the serial plate, must
not exceed the rated input by more than 5%.
4. To prevent premature heat exchanger failure, check to
be sure the blower has been set to deliver the proper
airflow for the application. Refer to page 19 for Blower
Adjustments.
5. Start-up and adjustment procedures must be performed
by a qualified service agency.
6. All scroll compressors requires the correct supply power
phase rotation. Phase reversal may result in compressor
failure not covered under warranty.
7. All refrigeration checks must be made by a qualified
R-410A refrigeration technician.
8. Do not release refrigerant to the atmosphere. When
adding or removing refrigerant, all national, state/
province, and local laws must be followed.
9. On units with the electric preheat option, to prevent
premature heat exchanger failure, check to be sure the
blower has been set to deliver the proper airflow for the
application. Refer to page 19 for Blower Adjustments.
10. The exhaust fan is not designed for high temperature
or smoke control exhaust applications. Exhaust air
temperature must not exceed 104°F. Operating the
exhaust fan above 104°F will result in failure of the
exhaust fan.
To Convert Multiply By To Obtain
To Convert Multiply By To Obtain
CFH
1.699
m3/min
“W.C.
0.24
kPa
Btu/ft3
0.037
mJ/m3
psig
6.893
kPa
pound
0.453
kg
°F
(°F-32) x 0.555
°C
Btu/hr
0.000
kW/hr
inches
25.4
mm
gallons
3.785
liters
feet
0.305
meters
psig
27.7
“W.C.
CFM
0.028
m3/min