6. Test run

Fig. 6-2

Water supply pump
Water (about 1000cc)
Drain plug
Pour water through outlet

. Be careful not to spray water

    into the drain pump mechanism.




6.3.  Check of drainage (Fig. 6-2)

• Ensure that the water is being properly drained out and that no water is leaking 

from joints.

When electric work is completed.

. Pour water during cooling operation and check.

When electric work is not completed.

. Pour water during emergency operation and check.
* Drain pan and fan are activated simultaneously when single phase 208/230V is 

turned on to L1 and L2 on terminal block after the connecter (SWE) on controller 
board in the electrical branch box is set to ON.

Be sure to turn it back to the former state after work.

Fig. 6-1

  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

"

.  

6.1.  Before test run

  After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase 
in the supply.

  Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0 M

"

.

6.2

Test run

Using Simple 

MA

 remote controller (Fig. 6-1)

1  

Before making a test run, refer to the “Test Run” section of the indoor unit 
installation manual.

2  

When the [ON/OFF] button and [TEMP.   ] button are pressed simultaneously 
for 2 seconds or longer, test run is performed.

 

Stop the test run by pressing the [ON/OFF] button.

4  

If an error code is displayed on the remote controller or if the air conditioner 
does not operate properly, refer to the outdoor unit installation manual or other 
technical materials.

.

 ON/OFF lamp

The lamp will light up in green when 
turned on, and blink during startup 
and when an error occurs.

Backlit LCD

button

button

 TEMP. 
 MODE

button

 ON/OFF

Pressing this button starts and 
stops the operation.

button

 FAN

button

 VANE

COOL
  VENTI.

Indoor unit piping temperature

Display range: -4ºF (-20ºC) to 158ºF 
(70ºC)
“-4ºF” or “158ºF” flashes on the 
display.

Test run time

The remaining time for test run 
is displayed.
Display range: 2:00 to 0:01
After two hours, the test run 
stops automatically.

Содержание PLFY-P-NBMU-E2

Страница 1: ...r conditioner unit FOR INSTALLER MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil ext rieur pour une utilisation s r...

Страница 2: ...s authorized by Mitsubishi Electric and ask the dealer or an authorized technician to install them Do not touch the heat exchanger fins Install the air conditioner according to this Installation Manua...

Страница 3: ...e duct holes cut out located at the positions shown in Fig 2 3 as and when required A fresh air intake hole for the optional multi function casement can also be made Note The figure marked with in the...

Страница 4: ...etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of the suspension bolts securely...

Страница 5: ...for grouped piping 9 mm or more insulation J Up to 850 mm 33 7 16 inch 1 Connect the drain socket supplied with the unit to the drain port Fig 3 5 Fix the tube using PVC adhesive then secure it with...

Страница 6: ...rrent sensitivity 3 F0 20A or less 2 3 3 12 3 3 12 3 3 12 20 20 20 20A current sensitivity 3 F0 30A or less 2 5 3 10 5 3 10 5 3 10 30 30 30 30A current sensitivity 3 Apply to IEC61000 3 3 about max pe...

Страница 7: ...ecting remote controller indoor and outdoor transmission cables Fig 4 3 Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For sp...

Страница 8: ...P08 P30NBMU E2 SWA SWB 1 2 3 Silent Standard High ceiling 4 4 direction 2 5 m 8 2 ft 2 7 m 8 9 ft 3 5 m 11 5 ft 3 3 direction 2 7 m 8 9 ft 3 0 m 9 8 ft 3 5 m 11 5 ft 2 2 direction 3 0 m 9 8 ft 3 3 m 1...

Страница 9: ...e corner panel Fig 5 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 5 3 5 4 A Intake grille B Grille C Intake...

Страница 10: ...up or down orientations depending upon the environment of use Set according to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed u...

Страница 11: ...ooseness in the power sup ply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt megohmmeter to check that the resistance between the power supply terminal...

Страница 12: ...Electric et de mander votre revendeur ou une soci t agr e de les installer Ne touchez jamais les ailettes de l changeur de chaleur Installez le climatiseur en respectant les instructions du manuel d i...

Страница 13: ...st risque sur le sch ma repr sente les dimensions de l appareil principal sans tenir compte des dimensions du bo tier multifonctions disponible en option Lors de l installation de ce bo tier multifonc...

Страница 14: ...en vinyle rempli d eau v rifier que l appareil principal soit bien l horizontale Lorsque la bonne position de l appareil principal est d finie avec certitude serrer convenablement les crous des boulo...

Страница 15: ...33 7 16 pouces 1 Raccorder la prise d ecoulement fourni avec l appareil au port de drainage Fig 3 5 Apposer le tube l aide de ruban adh sif en PVC puis le fixer avec une sangle 2 Installer un tuyau de...

Страница 16: ...doit tre assur par l installation de climatisation Fig 4 2 A Disjoncteur de fuite la terre B Commutateur local Disjoncteur C Appareil int rieur D Bo te de tirage Fig 4 1 D C TB2 TB5 TB15 S 1 2 M1 L1...

Страница 17: ...Raccorder l unit int rieure TB5 et l unit int rieure TB3 2 fils non polaris s Le S sur l unit int rieure TB5 est une connexion pour c bles blind Pour les sp cifications techniques des c bles de connex...

Страница 18: ...bon positionnement de l interrupteur curseur marqu SWA et SWB pour viter tout probl me de refroidissement chauffage PLFY P08 P30NBMU E2 SWA SWB 1 2 3 Silencieux Standard Haut plafond 4 4 directions 2...

Страница 19: ...our le d poser Fig 5 3 5 4 A Grille d admission B Grille C Leviers de la grille d admission D Crochet de la grille E Orifice pour le crochet de la grille F Panneau en coin G Vis H D tail 5 3 S lection...

Страница 20: ...t l commande 1 Mettre l interrupteur principal hors tension Si le ventilateur de l appareil devait fonctionner vous risqueriez de vous blesser ou de recevoir une d charge lectrique 2 D brancher le con...

Страница 21: ...surer que la r sistance entre les terminaux d alimentation lectrique et la terre soit au moins de 1 0 M A Pompe d arriv e d eau B Eau environ 1000 cc C Bouchon de vidange D Verser l eau travers le con...

Страница 22: ...en este manual de instalaci n Todas las conexiones el ctricas deber n ser realizadas por un electricista autorizado de acuerdo con la normativa local Si el aire acondicionado se instala en una habitac...

Страница 23: ...e fresco para la caja multifuncional opcional Nota Las cifras marcadas mediante en el gr fico representan el tama o de la uni dad principal sin tener en cuenta la caja multifuncional opcional Cuando i...

Страница 24: ...ue la unidad principal est nivelada horizontalmente mediante un nivel o tubo de vinilo relleno de agua Una vez comprobada la posici n de la unidad principal apriete firmemente las tuercas de los torni...

Страница 25: ...3 7 16 pulgadas 1 Conecte el tubo de desag e suministrado con la unidad al orificio de desag e Fig 3 5 Sujete el tubo con cinta aislante y asegure la conexi n con una abrazadera 2 Instale un tubo de d...

Страница 26: ...0 20 A o menos 2 3 3 12 3 3 12 3 3 12 20 20 20 Sensibilidad de corriente de 20 A 3 F0 30 A o menos 2 5 3 10 5 3 10 5 3 10 30 30 30 Sensibilidad de corriente de 30 A 3 Apl quese el IEC61000 3 3 para la...

Страница 27: ...ia y de las unidades exterior e interior Fig 4 3 Conecte TB5 de la unidad interior y TB3 de la unidad exterior cable no polari zado de 2 hilos La S en TB5 de la unidad interior indica una conexi n de...

Страница 28: ...sici n correcta ya que de no estarlo podr an producirse problemas como la falta de expulsi n de aire PLFY P08 P30NBMU E2 SWA SWB 1 2 3 Silencio Est ndar Techo alto 4 4 direcciones 2 5 m 8 2 pies 2 7 m...

Страница 29: ...5 4 A Rejilla de admisi n B Rejilla C Palancas de la rejilla de admisi n D Gancho de la rejilla E Orificio para el gancho de la rejilla F Panel angular G Tornillo H Detalle 5 3 Selecci n de las salid...

Страница 30: ...posici n indicada en el con trolador remoto 1 Apague el interruptor principal Pueden producirse da os o descargas el ctricas mientras gire el ventilador de la unidad 2 Desconecte el conector del moto...

Страница 31: ...alimentaci n Utilice un megaohm metro de 500 V para comprobar que la resistencia en tre los bornes de alimentaci n y la tierra es como m nimo de 1 0 M A Bomba de alimentaci n de agua B Agua aprox 100...

Страница 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in JAPAN RG79D308K06 HEAD OFFICE T...

Отзывы: