69
-
'11 • KX-T-166
(1)
External input and demand input
(a) Operation permission and prohibition modes
(Note) With 7-segment display [P07]-[0]
1)
Operation permission or operation prohibition mode is switched with the connector (CnS1) and the jumper wire (J13)
on the outdoor PCB.
J13: Switching of CnS1 input method
J13 short-circuited: CNS1 is for the level input.
J13 open: CnS1 is for the pulse input.
2)
Operation permission/prohibition control by the external input CnS1 of outdoor unit
Input: CnS1
Switching with J13
CnS1: Switching of operation permission/
prohibition modes
Short-circuit
Open
Short-circuit (Level input) Operation prohibition mode
Operation permission mode
Open (Pulse input)
Switching of operation permission/
operation prohibition modes (Reversal)
Open
Short-circuit
Short-circuit (Level input) Operation permission mode
Operation prohibition mode
Open (Pulse input)
(NOP)
Note (1) Factory setting – J13: Short-circuit, CnS1: Short-circuit (Short-circuit pin connected)
3)
The operation condition is desplayed on the LCD of remote controller and is transferred to optional centralised
controller.
4)
When the control comand from remote controller is not accepted (Under the condition of the system all stop status
by external input), “Center” is dispalyed. See Item 5) mentioned below.
5)
CnS1 performs the following operations depending on the short-circuit or open of the jumper wire (J13). In case of
pulse input, the pulse width is 500ms or larger.
J13 – Short-circuit
CnS1 input OFF (Open)
Remote controller operation
Remote controller display
Air-conditioner operation/stop
PUSH
PUSH
PUSH
PUSH
OFF
ON (Short-circuit)
OFF (Open)
OFF
OFF
ON
ON
Air-conditioner ON OK
Center
Center
Remote
J13 - Open
CnS1 input
Remote controller operation
Remote controller display
Air-conditioner operation/stop
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
Air-conditioner ON OK
Center
Remote
Center
Center
Remote
PUSH
PUSH
PUSH
PUSH PUSH
(b) Demand control
(Note) With 7-segment [P07] = [1]
1)
Demand control and normal operation are switched with the dip switches (SW4
‒
5,4
‒
6) and the jumper wire (J13)
on the outdoor PCB.
J13 short-circuit: CnS1 is for the level input
J13 open: CnS1 is for the pulse input