115
-
'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E10
-
Excessive number of indoor units (moe than 17 units)
by controlling one remoto controller
Keeps flashing Stays Off
Keeps flashing Stays Off
1.Applicable model
5.Troubleshooting
All models
Diagnosis
Countermeasure
Aren't more
than 17 indoor units
connected to one remote
controller?
NO
YES
Remote controller anomaly
Replace it.
Reduce to 16 or less units.
2.Error detection method
When it detects more than 17 of
indoor units connected to one
remote contorller
3. Condition of error displayed
Same as above
4.Presumable cause
• Excessive number of indoor
units connected.
• Remote controller anomaly.
Note: