119
-
'11 • KX-T-166
Address setting error of
master and slave indoor units
Keeps flashing
Keeps flashing Stays Off
1 time flash
1. Applicable model
5. Troubleshooting
All models
Address setting error of the
master indoor unit
No power supply to the master
indoor unit
No connection of superlink
signal wires between master
and slave indoor unit.
Diagnosis
Countermeasure
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
NO
NO
NO
NO
YES
YES
YES
Is the power
surely supplied to the master
indoor unit ?
Is the address
setting for the master indoor
unit correct?
Correct the address setting of
the master indoor unit
Supply the power to the master
indoor unit
Connect the superlink signal
wires correctly
㪅㩷
Indoor control PCB anomaly
→ Replace it
(Firstly replace PCB on the
slave indoor unit. If it is not
recovered, replace PCB on
the master indoor unit as well.)
Are the superlink
signal wires connected between
master and slave
indoor units?
(1) When the address setting for
the master indoor unit is not
existing in the same superlink
system.
(2) When the address setting for
the slave indoor unit is set for
the master indoor unit
redundantly.
Same as above
Address setting error of
master and slave indoor units
Keeps flashing
Keeps flashing Stays Off
1 time flash
E18
-
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content