79
-
'11 • KX-T-166
Code
No.
Contents of data display
Data display range Minimum
unit
Remarks
C32 External input
0,1
(0: Open, 1: Close)
–
Order of 100: CNG2
Order of 10: (Spare)
Order of 1: (Spare)
C33 Relay output
0,1
(0: Open, 1: Close)
–
Order of 100: 52C-1
Order of 10: 20S
Order of 1: Crankcase heater 1
C34 Relay output
0,1
(0: Open, 1: Close)
–
Order of 100: SV6
Order of 10: (Spare)
Order of 1: (Spare)
C35 Relay output
0,1
(0: Open, 1: Close)
–
Order of 100: SV1
Order of 10: SV11
Order of 1: SV12
C36 Relay output
0,1
(0: Open, 1: Close)
–
Order of 100: (Spare)
Order of 10: (Spare)
Order of 1: (Spare)
C37 External output
0,1
(0: Open, 1: Close)
–
Order of 100: External output (CNZ1)
Order of 10: CnH Operation output
Order of 1: CnY Anomalous output
C38 (Spare)
–
–
C39 (Spare)
–
–
<Outdoor unit information>
C40 Number of connected indoor units
0 ~ 50
1
C41 Capacity of connected indoor units
0 ~ 200
1
C42 Number of indoor units with thermostat ON
0 ~ 50
1
C43 Required Hz total
0 ~ 999
1Hz
C44 Cumulative compressor operation time
(CM1)
0 ~ 655
100h
C45 (Spare)
C46 Discharge pressure saturated temperature
-50 ~ 70
0.1°C
Range unable to display (-10°C or under) is in the unit of 1°C.
C47 Suction pressure saturated temperature
-50 ~ 30
0.1°C
Range unable to display (-10°C or under) is in the unit of 1°C.
C48 Sub-cooling coil temperature sensor 1
saturated pressure
-0.68 ~ 4.15
0.01
MPa
0 is omitted in negative range.
-0.68
[-.68]
C49 Super cooling
0 ~ 50
0.1deg
C50 Super heat
0 ~ 50
0.1deg
C51 Sub-cooling coil overheat
0 ~ 50
0.1deg
C52 Discharge pipe overheat 1
0 ~ 50
0.1deg
C53 Under-dome overheat 1
0 ~ 50
0.1deg
C54 Target cooling low pressure
0.00 ~ 2.00
0.01MPa
C55 Target heating high pressure
1.60 ~ 4.15
0.01MPa
C56 Target Fk
0 ~ 999
1Hz
C57 Inverter 1 operation frequency command
0 ~ 130
1Hz
C58 (Spare)
0 ~ 130
1Hz
C59 FMo1 Fan Speed command
0 ~ 999
10min-1
C60 FMo2 Fan Speed command
0 ~ 999
10min-1