RANGE OF USAGE & LIMITATIONS
Allowable length of refrigerant piping, height difference between indoor and outdoor unit
(1) Branch pipe method (using branch piping)
(2) Header System (Header used)
Note () A branch piping system cannot be connected after a header system.
(2) 90m or less (However, difference between the longest and shortest piping : 40m or less)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
First branch
50m
MAX.
90m
MAX. 90m
MAX. 90m
MAX. 15m
(Outdoor unit is lower : 40m
)
MAX.
130m
50m
MAX.
130m
MAX. 15m
MAX. 18m
MAX. 18m
MAX. 18m
MAX. 18m
(Outdoor unit is lower : 40m
)
(Lowest indoor unit)
(Highest indoor unit)
(Highest indoor unit)
(Lowest indoor unit)
First branch
(Header)
denotes
System
FDCR280KXE6
Please see the next page.
1 to 16 unit
1 to 13 unit
Item
Indoor intake air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Single direction piping length
Actual length : 160m or less, Eguivalent length : 185m or less
Total piping length
Main pipe length
510m or less
130m or less
90m or less (However, difference between the longest and shortest piping : 40m or less)
6 min or more (3 minutes or more from start to stop or 3 minutes or more from stop to start)
3 min or more
Within 10% of rated voltage
50m or less
40m or less
15m or less
Allowable pipe length from the first branching
18m or less
Elevation difference between the first branching point and the indoor unit
Number of connected units
Connectable capacity
(1)
FDCR224KXE6
112 ~ 292
140 ~ 364
Outdoor unit is higher
Outdoor unit is lower
Indoor units
that can be
used in
combination
Difference in
height between
indoor and outdoor
units
Difference in the elevation of indoor units in a system
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDQS, FDUH
1 cycle time
Stop time
Voltage fluctuation
Phase unbalance
Compressor
stop/start
frequency
Power source
voltage
Voltage drop during start
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU : Dew point temperature 23 or less, relative humidity 80% or less)
Within 3% of rated voltage
Within 15% of rated voltage