'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E40
E40
High pressure anomaly
(63H1-1activated)
Keeps flashing Stays Off
Keeps flashing 1 time flash
1.Applicable model
5.Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
YES
YES
NO
Save data for 30 minutes before stopping in Mente PC
Connect a pressure gauge and
restart operation.
YES
YES
NO
Was 63H1
activated at 4.15MPa
or higher?
Does the sensed
value of the high pressure
sensor show 4.15MPa?
(Normal?)
Are the
63H1-1 OK?
Are the connector and/or
harnesse
OK?
NO
Are the
service valves fully
open?
YES
Is it
stop at 4.15MPa of gauge
pressre ?
Is there any
clogging in the refrigerant
circuit ?
NO
NO
NO
YES
Check and save the data of
operating condition
Check the sensed value of
high pressure sensor when the
63H1-1 is activated
Check whether the high
pressure switch is activated
at the sensed value of high
pressure sensor.
High pressure sensor
anomaly is suspicious.
Check high pressure sensor
itself according to the
troubleshooting procedure of
E54, after retarting operation.
(If the high pressure sensor
[PSH] fails, replace it)
If the connector is
disconnected or the harness
is broken, correct it.
Also check whether the
high pressure switch is
properly
mounted or not
Open operation valve.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Replace outdoor control
PCB.
Remove clogs.
Check items (condenser
side):
• Filter clogging
• Airflow volume (Fan
motor)
• Short-circuit of airflow
2.Error detection method
When high pressure switch
63H1-1 is activated
3. Condition of error displayed
• If high pressure exceeds
4.15MPa
• If 63H1-1 is activated 5 times
within 60 minutes
• If 63H1-1 is activated for 60
minutes continuously
4.Presumable cause
• Short-circuit of airflow
at condenser side of heat
exchanger/Disturbance of
airflow/Clogging filter/Fan
motor anomaly
• Disconnection of high
pressure switch connector
• Breakage of high pressure
switch harness
• Closed service valves
• High pressure sensor anomaly
• High pressure switch anomaly
Note:
If the error does not recur, connect the Mente PC and continue to collect data.