146
-
'11 • KX-T-166
j
PCB012D017A
8.4 Outdoor unit control PCB replacement procedure
(Note) If cut the tie, the wiring cables should be bound with new tie again.
Exchange the control PCB according to the following procedure.
1. Replace the control PCB after elapsing 3 minutes from power OFF.
(Be sure to measure voltage (DC) at both capacitor terminals (1. Power supply for PCB 2. Power supply for fan motor)
and check that the voltage is discharged completely. (Refer to Fig.1))
2. Disconnect the connectors from the PCB.
3. Disconnect the blue wiring passing through CT1 on the PCB before replace the coutrol PCB.
4. Set the setting switches (SW1-6) of new PCB same as previous PCB.
5. Tighten up a screw after passing blue wiring through CT1 of the changed.
6. Connect the connectors to the PCB. (Contirm the connectors are not half inserted.)
After elapsing 3 minutes
from power OFF
CNQ3
2
CT1
CNN2
CNTH
CNEEV1
CNN9
CNL1
CNFAN_2
CNR1
CNB2
CNEEV2
CNQ1
CNFAN_1
CNN
CNN4
6
CNW
CNM1
CNN1
Parts arrangement view
1 Reuse the parts used before the PCB exchange.
2 Please do not carry out wrong insertion.
The PCB will be destroyed if a mistake is made
in putting CNA2 (brown) and CNQ3 (yellow).
CNA2
CNQ3
CNI
CNA2
2
CN 2
CNS1
CNS2
CNG1
CNG2
CNX1
CNU1
CNF2
CNF1
CNP1
Precautions for Safety
Since the following precaution is the important contents for safety, be sure to observe them.
WARNING and CAUTION are described as follows:
Indicates an imminently hazardous situation which will result in death or serious injury if
proper safety procedures and instructions are not adhered to.
Indicates a potentially hazardous situation which may result in minor or moderate injury
if proper safety procedures and instructions are not adhered to.
WARNING
Securely replace PCB according to this following instruction.
If PCB is incorrectly replace, it will cause an electric shock or -re .
Be sure to check that the power source for the outdoor unit is turned OFF before replace PCB,
The PCB replacement under current-carrying will cause an electric shock.
After -nishing PCB replacement, check that wiring is correctly c onnected with the PCB before power
distribution, If PCB is incorrectly replace, it will cause an electric shock or -re.
CAUTION
Bundle the wiring so as not to tense because it will cause an electric shock.
WARNING
CAUTION