61
-
'11 • KX-T-166
(c)
Heating
→
Cooling
(i)
Start conditions
• When the outdoor unit operation mode is changed from the heating operation to cooling operation
(ii)
Control contents
1) When the compressor is operating, it makes the compressor stopped.
2) Each functional component operates according to the sequence shown below.
(iii)
End conditions
• End of sequence
Note (1)
※
: It is fully closed till the end of 3-minute delay after the automatic reset.
• Meaning of marks
CM
FMo1, FMo2
20S
EEVH
EEVSC
ON
Heating
Cooling
15 seconds
3 minutes
Initial opening
Fully closed
(※)
Time
Start conditions established
Normal control
Initial speed
Fully closed
OFF
OFF
Fully open
Any state
Any state
Any state
CM
Compressor
EEVH
Heating electronic expansion valve
FMo1, FMo2 Fan motor
EEVSC
Subcooling coil electronic expansion valve
20S
4-way solenoid valve
―
―――