88
–
'14 • KX-SM-200
Error code
Remote control:
E20
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
Indoor DC fan motor
Keeps flashing
1(2)-time
fl
as
h
Keeps flashing
Stays OFF
1.Applicable model
5.T
roubleshooting
FDT, FDTC, FDTW, FDTS,
FDU, FDUM, FDUT71, FDK,
FDFW, FDU-F series only
Diagnosis
Countermeasure
NO
YES
YES
YES
Does any
foreign material
intervene in rotational area
of fan propeller?
Is DC280V detected
between
①-④(①-③,⑥-④)
of fan power PCB connector
CNM?
Is it normalized?
( Is DC280V detected between
⑥-④
of
motor control PCB
connector CNM? )
Is the fuse F1,F2,F3
blown?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
NO
YES
Note(1)
④
or
③
for GND
Note(2) Value in (
①-③
) are for the models
FDK, FDFW
Value in (
⑥-④
) are for the models
FDU224,280KXZE1 and
FDU1800,2400FKXZE1
Note(3) FDU224,280KXZE1 and
FDU1800,2400FKXZE1 (FM1)
only.
YES
Power source reset
NO
Remove foreign material.
Replace the fan moto
r.
Check power voltage.
Replace faulty fan motor
and power PCB.
Replace harness assy
between motor PCB and
power PCB.
Replace fan motor.
[
If the error persists after
replacing the fan motor,
replace the indoor control
PCB.
(FDU224,280KXZE1 and
FDU1800,2400FKXZE1
(FM1) : Motor contrl PCB)]
Malfunction by temporary
noise.
2.
Error detection method
Detected by rotation speed of
indoor fan motor
3
.Condition of Error displayed
•
When the actual fan rotation
speed does not reach to the
speed of [required speed
-50 (FDU: -500) min
-1
] after 2
minutes have been elapsed since
the fan motor rotation speed
command was output, the unit
stops by detecting indoor fan
motor anomaly.
4. Presumable cause
•Defective indoor power (control)
PCB
•Foreign material at rotational
area of fan propeller
•Defective fan motor
•Dust on control PCB
•Blown fuse
•External noise, surge
Note:
Note (1) Value in (
) is for the FM2 onl
y.
(1),(2)
Is DC280V
detected between
⑥-④
of
motor control PCB connector
CNM?
(3)
(4)
Note(4) Value in ( ) are for the models
FDU224,280KXZE1 and
FDU1800,2400FKXZE1 (FM1)
only.
(FDT, FDTC, FDTW, FDTS, FDU, FDUM
FDUT71, FDK, FDFW, FDU-F series)
rotation speed anomaly