87
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
E19
–
Indoor unit operation check,
drain motor check mode anomaly
Keeps flashing 1-time flash
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Indoor control PCB
anomaly
(Anomalous SW7)
Replace.
Turn SW7-1 on the indoor
control PCB OFF and reset
the power.
2. Error detection method
E19 occurs
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
Due to forgetting to turn OFF
SW7-1 after indoor operation
check)
Note:
Indoor operation check/drain pump check mode
If the power is ON after SW7-1ON, indoor operation check/drain pump check mode can be established.
1) When the communication between remote control and indoor PCB is established 15 seconds after power ON, it goes to
indoor operation check.
2) When the communication between remote control and indoor PCB is not established, it goes to drain pump check.
(CnB connector should be open before power ON.)
Is SW7-1
on the indoor control
PCB ON?
E19 occurs when the
power ON
NO
YES