'14 • KX-SM-200
–
113
–
Fig.1 Part Arrangement View
2.4 Heat source unit control PCB replacement procedure
Exchange the control PCB according to the following procedure.
1. Exchange the PCB
after elapsing 3 minutes from power OFF.
(
Be sure to measure voltage (DC)
and
check that the voltage is discharged sufficiently.
(Refer to Fig.2 ))
2. Disconnect the connectors from the PCB.
3. Disconnect the blue wiring passing through CT1 on the PCB before exchanging the PCB.
4. Match the setting switches (SW1-6) and jumper wires (J11-16) with the former PCB.
5. Tighten up a screw after passing blue wiring through CT1 of the changed.
6. Connect the connectors to the PCB. (Confirm the
connectors are not half inserted.
)
Precautions for Safety
●
Since the following precaution is the important contents for safety, be sure to observe them.
WARNING and CAUTION are described as follows:
Indicates an imminently hazardous situation which will result in death or serious injury
if proper safety procedures and instructions are not adhered to.
Indicates a potentially hazardous situation which may result in minor or moderate injury
if proper safety procedures and instructions are not adhered to.
WARNING
●
Securely exchange the PCB according to this procedure.
If the PCB is incorrectly exchanged, it will cause an electric shock or fire.
●
Be sure to check that the power source for the outdoor unit is turned OFF before exchanging the substrate.
The PCB exchange under current-carrying will cause an electric shock or fire.
●
After finishing the PCB exchange, check that wiring is correctly connected with the PCB before power distribution.
If the PCB is incorrectly exchanged, it will cause an electric shock or fire.
CAUTION
●
Band the wiring so as not to tense because it will cause an electric shock.
WARNING
CAUTION
PCB012D045B
CNQ3
CNQ1
CNW
CNEEV4
CNEEV2
CNEEV3
CNEEV1
SW3 SW5
SW4 SW6
SW1 SW2
J11-16
CNX1
Parts No.
CNTH
CT1
CN15
CNL3
CN16
CNB2
CNU1
CNF2
CNF1
CNP1
CNL1
CNL2
CNB3
CNS1
CNS2
CNG1
CNG2
CNN14
CNN13
CNN10 CNN5 CNN11
CNN9
CNN6 CNR1
CNN4 CNN8 CNN2 CNM1
CNN1
CNI1
(※1)