'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
E1
–
Remote control
communication error
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the power
source reset?
Does
the drain pump start
automatically at one
minutes after power
ON?
Turn SW7-1 OFF.
→
ON
Disconnect the wire
③
between indoor and heat
source units.
YES
YES
NO
Note (1) SW7-1: OFF
→
ON
Note (2) Does the remote control displays “Internal check ON” even
after 3 minutes?
Reset power source
(2)
(1)
NO
Malfunction by temporary
noise.
Check peripheral
environment.
Indoor control PCB
anomaly
Replace it.
Remote control
anomaly
Replace it.
2. Error detection method
When normal communication
between remote control and
indoor unit is interrupted
for more than 2 minutes.
(Detectable only with the
remote control.)
3. Condition of error displayed
Same as above
4. Presumable cause
• Anomalous communication
circuit between remote control
and indoor unit.
• Noise
Note:
If the indoor unit cannot communicate normally with the remote control for 180 seconds, the indoor unit PCB starts to
reset automatically.