E54
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
NO
YES
Replace the low pressure sensor.
Are the
connection of low pressure
sensor connectors (at sensor side
and PCB side) OK?
Are the
pressure (actual
measurement) matched with the value
indicated on the remote
controller?
Is
normal condition
restored?
NO
YES
Correct low pressure sensor
connector connection.
Is refrigerant amount
charged properly?
Is there any anomaly on the
refrigeration circuit?
Defective outdoor control
PCB
➞
Replace.
(Defective low pressure
sensor input circuit)
OK
2. Error detection method
When anomalous voltage
(pressure) is detected
3.
Condition of Error displayed
If the pressure sensor detects 0V
or lower and 3.49V or higher for
5 seconds continuously within
2 minutes to 2 minutes 20
seconds after compressor ON,
the compressor stops. When
the compressor is restarted
automatically after 3-minuts
delay, if this anomaly occurs 3
times within 40 minutes
4. Presumable cause
• Defective low pressure sensor
connection
• Defective low pressure sensor
• Defective outdoor control
PCB
• Improper amount of
refrigerant
• Anomalous refrigeration
circuit
Note:
Error code
Remote controller:
Content
1 time flash
Keeps flashing
Keeps flashing
–
–
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor
control PCB
Outdoor
inverter PCB
Low pressure sensor anomaly
-
449
-
'12 • PAC-T-174
Содержание SRK100VNPZJX
Страница 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Страница 96: ... 95 12 PAC T 174 b Ceiling cassette 4way compact type FDTC Models FDTC50VF 60VF G G G D A B C F G c PJA003Z338 ...
Страница 97: ... 96 12 PAC T 174 c Ceiling suspended type FDEN Model FDEN50VF C2 C1 A B F E G D A B C1 C2 C1 C2 PFA003Z816 B ...
Страница 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Страница 99: ... 98 12 PAC T 174 Models FDEN100VF 125VF 140VF A C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z818 B ...
Страница 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Страница 112: ... 111 12 PAC T 174 Model RC EX1A Installation space R C cable 0 3mm2 2 core Adapted to RoHS directive a PJZ000Z297 ...
Страница 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Страница 266: ... 265 12 PAC T 174 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL PJZ012D077 a ...
Страница 274: ... 273 12 PAC T 174 1 10 4 Installation of outdoor unit 1 Models FDC100 140VN 100 140VS page 204 PSB012D923D J ...
Страница 275: ... 274 12 PAC T 174 ...
Страница 276: ... 275 12 PAC T 174 ...
Страница 277: ... 276 12 PAC T 174 ...
Страница 286: ... 285 12 PAC T 174 ...
Страница 287: ... 286 12 PAC T 174 ...
Страница 288: ... 287 12 PAC T 174 ...
Страница 338: ... 337 12 PAC T 174 Model FDEN series Replace and set up the PCB according to this instruction PSB01ZD974B ...
Страница 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Страница 507: ... 506 12 PAC T 174 3 6 SUPER LINK E BOARD SC ADNA E SL2NA E and SL3N AE BE to control PJZ012D029F ...
Страница 508: ... 507 12 PAC T 174 ...