'12 • PAC-T-174
INSPECT I/U
INSPECT I/U
(When 1 or 2 remote controllers are connected)
Keeps flashing
Stays OFF
Keeps flashing 2 times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Are 2 units
of remote controller
connected?
Is it set
at the slave remote
controller?
⑴,
⑵
Note (1) Use SW1 to set at
master or slave.
Note (2)
“Slave” is displayed
on the remote
controller LCD.
⑵
Does it
become normal?
Do more than
one indoor units have the
same address?
Are remote
controller wires laid
along high voltage
wires?
Does DM
start 60 seconds later
automatically.
Disconnect the connecting
wire
�
between the indoor
and outdoor unit.
Power supply reset
NO
YES
YES
NO
NO
NO
NO
NO
YES
YES
YES
Set one remote controller
for “Master” and the other
for “Slave”
Set SW1 on remote
controller PCB at “Master”.
Set address again. (SW2 on
indoor control PCB)
Separate remote controller
wires from high voltage
wires.
Defective indoor control
PCB
➞
Replace.
Defective remote controller
➞
Change.
2. Error detection method
Communication between indoor
unit and remote controller
is disabled for more than 30
minutes after the power on.
3. Condition of Error displayed
Same as above
4. Presumable cause
• Improper setting
• Surrounding environment
• Defective remote controller
communication circuit
• Faulty indoor control PCB
Note:
If any error is detected 30 minutes after displaying “
WAIT
” on the remote controller, the display changes to
“INSPECT I/U”.
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
368
-
Содержание SRK100VNPZJX
Страница 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Страница 96: ... 95 12 PAC T 174 b Ceiling cassette 4way compact type FDTC Models FDTC50VF 60VF G G G D A B C F G c PJA003Z338 ...
Страница 97: ... 96 12 PAC T 174 c Ceiling suspended type FDEN Model FDEN50VF C2 C1 A B F E G D A B C1 C2 C1 C2 PFA003Z816 B ...
Страница 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Страница 99: ... 98 12 PAC T 174 Models FDEN100VF 125VF 140VF A C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z818 B ...
Страница 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Страница 112: ... 111 12 PAC T 174 Model RC EX1A Installation space R C cable 0 3mm2 2 core Adapted to RoHS directive a PJZ000Z297 ...
Страница 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Страница 266: ... 265 12 PAC T 174 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL PJZ012D077 a ...
Страница 274: ... 273 12 PAC T 174 1 10 4 Installation of outdoor unit 1 Models FDC100 140VN 100 140VS page 204 PSB012D923D J ...
Страница 275: ... 274 12 PAC T 174 ...
Страница 276: ... 275 12 PAC T 174 ...
Страница 277: ... 276 12 PAC T 174 ...
Страница 286: ... 285 12 PAC T 174 ...
Страница 287: ... 286 12 PAC T 174 ...
Страница 288: ... 287 12 PAC T 174 ...
Страница 338: ... 337 12 PAC T 174 Model FDEN series Replace and set up the PCB according to this instruction PSB01ZD974B ...
Страница 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Страница 507: ... 506 12 PAC T 174 3 6 SUPER LINK E BOARD SC ADNA E SL2NA E and SL3N AE BE to control PJZ012D029F ...
Страница 508: ... 507 12 PAC T 174 ...