327
-
'12 • PAC-T-174
1.12 MAINTENANCE DATA
1.12.1 Diagnosing of microcomputer circuit
(1)
Selfdiagnosis function
(a) Check Indicator Table
Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote controller error code,
indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
Note (1) SRK series only.
At the indoor unit side, errors are displayed with the combination of RUN light and TIMER light on the display panel.
(i)
Indoor unit
1)
FDT, FDTC, FDEN, FDU, FDUM, FDF series
Remote controller
Indoor control PCB
Outdoor control PCB
Location of
trouble
Description of trouble
Repair method
Reference
page
Error code
Red LED
Red LED
Green
LED (1)
Red LED
Green
LED (1)
No-indication Stays OFF
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
—
• Normal operation
—
—
Stays OFF Stays OFF
2 times
flash
Stays OFF Indoor unit power
supply
• Power OFF, broken wire/blown fuse, broken transformer wire
Repair
366
*
3 times
flash
Keeps
flashing Stays OFF
Keeps
flashing
Remote controller
wires
• Poor connection, breakage of remote controller wire * For wire breaking at power ON, the
LED is OFF.
Repair
367
Remote controller • Defective remote controller PCB
Replacement of
remote controller
WAIT
or
INSPECT I/U
Stays OFF
Keeps
flashing
2 times
flash
Keeps
flashing
Indoor-outdoor
units connection
wire
• Poor connection, breakage of indoor-outdoor units connection wire
Repair
368
-
372
Remote controller • Improper setting of master and slave by remote controller
Keeps
flashing
Stays OFF
*
Keeps
flashing Stays OFF
Keeps
flashing
Remote controller
wires (Noise)
•
Poor connection of remote controller signal wire (White)
•
Intrusion of noise in remote controller wire
* For wire breaking at power ON, the LED is OFF
Repair
374
Remote controller
indoor control PCB
*
• Defective remote controller or indoor control PCB (defective communication circuit)?
Replacement of
remote controller or
PCB
2 times
flash
Keeps
flashing
2 6 times
flash
Keeps
flashing
Indoor-outdoor
units connection
wire
•
Poor connection of wire between indoor-outdoor units during operation
(disconnection, loose connection)
•
Anomalous communication between indoor-outdoor units by noise, etc.
Repair
375
2 times
flash
Keeps
flashing Stays OFF
Keeps
flashing
(Noise)
•
CPU-runaway on outdoor control PCB
Power reset or
Repair
Outdoor control
PCB
*
• Occurrence of defective outdoor control PCB on the way of power supply (defective com-
munication circuit)?
Replacement of
PCB
2 times
flash
Keeps
flashing Stays OFF Stays OFF
Outdoor control
PCB
•
Defective outdoor control PCB on the way of power supply
Replacement
Fuse
•
Blown fuse
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Indoor heat
exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor
(defective element, bro-
ken wire, short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
376
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input
circuit)?
Replacement of
PCB
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Indoor return air
temperature therm-
istor
•
Defective indoor return air temperature thermistor
(defective element, broken wire,
short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
377
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input
circuit)?
Replacement of
PCB
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Installation or oper-
ating condition
•
Heating over-load
(Anomalously high indoor heat exchanger temperature)
Repair
378
Indoor heat
exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor (short-circuit)
Replacement of
temperature therm-
istor
Indoor control PCB
*
•
Defective indoor control PCB
(Defective temperature thermistor input circuit)?
Replacement of
PCB
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Drain trouble
•
Defective drain pump (DM), broken drain pump wire
, disconnected connector
Replacement, repair
of DM
379
Float switch
•
Anomalous float switch operation
(malfunction)
Repair
Indoor control PCB
*
•
Defective indoor control PCB
(Defective float switch input circuit)
*
•
Defective indoor control PCB
(Defective DM drive output circuit)?
Replacement of
PCB
Option
•
Defective optional parts
(At optional anomalous input setting)
Repair
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
Number of con-
nected indoor units
•
When multi-unit control by remote controller is performed, the number of
units is over
Repair
380
3 times
flash
Keeps
flashing Stays OFF
Keeps
flashing
Indoor unit No. set-
ting
•No master is assigned to slaves.
Repair
381
Rcmote controller wires •Anomalous remote controller wire connection, broken wire between master and slave units
1(2) time
flash
Keeps
flashing Stays OFF
Keeps
flashing
Fan motor
•
Defective fan motor
Replacement, repair
382
Indoor power PCB •
Defective indoor power PCB
Replacement
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Address
setting error
• Address setting error of master and slave indoor units
Repair
383
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing Indoor control PCB •
Improper operation mode setting
Repair
384
Содержание SRK100VNPZJX
Страница 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Страница 96: ... 95 12 PAC T 174 b Ceiling cassette 4way compact type FDTC Models FDTC50VF 60VF G G G D A B C F G c PJA003Z338 ...
Страница 97: ... 96 12 PAC T 174 c Ceiling suspended type FDEN Model FDEN50VF C2 C1 A B F E G D A B C1 C2 C1 C2 PFA003Z816 B ...
Страница 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Страница 99: ... 98 12 PAC T 174 Models FDEN100VF 125VF 140VF A C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z818 B ...
Страница 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Страница 112: ... 111 12 PAC T 174 Model RC EX1A Installation space R C cable 0 3mm2 2 core Adapted to RoHS directive a PJZ000Z297 ...
Страница 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Страница 266: ... 265 12 PAC T 174 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL PJZ012D077 a ...
Страница 274: ... 273 12 PAC T 174 1 10 4 Installation of outdoor unit 1 Models FDC100 140VN 100 140VS page 204 PSB012D923D J ...
Страница 275: ... 274 12 PAC T 174 ...
Страница 276: ... 275 12 PAC T 174 ...
Страница 277: ... 276 12 PAC T 174 ...
Страница 286: ... 285 12 PAC T 174 ...
Страница 287: ... 286 12 PAC T 174 ...
Страница 288: ... 287 12 PAC T 174 ...
Страница 338: ... 337 12 PAC T 174 Model FDEN series Replace and set up the PCB according to this instruction PSB01ZD974B ...
Страница 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Страница 507: ... 506 12 PAC T 174 3 6 SUPER LINK E BOARD SC ADNA E SL2NA E and SL3N AE BE to control PJZ012D029F ...
Страница 508: ... 507 12 PAC T 174 ...