434
-
E35
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Are the
characteristics of
outdoor heat exchanger
temperature thermistor
normal?
Is
the temperature
(measured actually) at
detection of error
correct?
NO
YES
YES
* For the contents of control, refer to the protective control by controlling
compressor rotation speed and cooling high pressure protective control of
micro computer control function for corresponding models.
Is the
unit operating in the
state of cooling
overload?
Is the high
pressure control
normal?
YES
NO
* For the characteristics of outdoor
heat exchanger temperature
thermistor, refer to E37.
YES
NO
NO
Replace outdoor heat
exchanger temperature
thermistor.
Check unit side.
• Isn’t the air circulation
of outdoor unit short-
circuited?
• Are installation spaces
adequate?
• Isn’t there any fouling
or clogging on heat
exchanger?
Control operation check *
Defective outdoor control
PCB
➞
Replace.
Excessive refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models.
3.
Condition of Error displayed
When outdoor heat exchanger
temperature anomaly is detected
5 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor heat
exchanger temperature
thermistor
• Defective outdoor control
PCB
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
• Excessive refrigerant amount
Note:
Error code
Remote controller:
Content
1 time flash
Keeps flashing
Keeps flashing
Keeps flashing
ON
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor
control PCB
Outdoor
inverter PCB
Cooling overload operation
-
434
-
'12 • PAC-T-174
Содержание SRK100VNPZJX
Страница 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Страница 96: ... 95 12 PAC T 174 b Ceiling cassette 4way compact type FDTC Models FDTC50VF 60VF G G G D A B C F G c PJA003Z338 ...
Страница 97: ... 96 12 PAC T 174 c Ceiling suspended type FDEN Model FDEN50VF C2 C1 A B F E G D A B C1 C2 C1 C2 PFA003Z816 B ...
Страница 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Страница 99: ... 98 12 PAC T 174 Models FDEN100VF 125VF 140VF A C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z818 B ...
Страница 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Страница 112: ... 111 12 PAC T 174 Model RC EX1A Installation space R C cable 0 3mm2 2 core Adapted to RoHS directive a PJZ000Z297 ...
Страница 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Страница 266: ... 265 12 PAC T 174 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL PJZ012D077 a ...
Страница 274: ... 273 12 PAC T 174 1 10 4 Installation of outdoor unit 1 Models FDC100 140VN 100 140VS page 204 PSB012D923D J ...
Страница 275: ... 274 12 PAC T 174 ...
Страница 276: ... 275 12 PAC T 174 ...
Страница 277: ... 276 12 PAC T 174 ...
Страница 286: ... 285 12 PAC T 174 ...
Страница 287: ... 286 12 PAC T 174 ...
Страница 288: ... 287 12 PAC T 174 ...
Страница 338: ... 337 12 PAC T 174 Model FDEN series Replace and set up the PCB according to this instruction PSB01ZD974B ...
Страница 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Страница 507: ... 506 12 PAC T 174 3 6 SUPER LINK E BOARD SC ADNA E SL2NA E and SL3N AE BE to control PJZ012D029F ...
Страница 508: ... 507 12 PAC T 174 ...