II
Restrictions ]
- 53 -
HWE0713A
GB
(3) Size of the pipe that fits the sub BC controller ports
The ports of the BC controller accommodates the pipes on P63-P140 models of indoor units. To connect other types of indoor
units, follow the procedure below.
1) To connect P15-P50 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the units between the P200 and P250 models of indoor units (or when the total capacity of indoor units is
P141 or above), use a junction pipe kit and merge the two nozzles.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P140 or below (in a system with a junction pipe: P250 or below)
Maximum number of connectable indoor units: 3 units
Branch joint: Use CMY-Y102S-G2 (optional accessory).
Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Select the proper size pipes for the main unit based on the total capacity of the indoor units that are connected to both sub
BC controllers. Select the proper size pipes for the sub controller side based on the total capacity of the indoor units that are
connected to the sub controller.
Unit : mm [inch]
Total capacity of indoor units
Liquid pipe
Gas pipe
P140 or below
ø9.52 [3/8"]
ø15.88 [5/8"]
P141 - P250
ø9.52 [3/8"]
ø19.05 [3/4"]
Unit : mm [inch]
Operation
Pipe sections
High-pressure side
(liquid)
Low-pressure side
(gas)
Liquid pipe side
Total capacity of the in-
door units that are con-
nected to the BC
controller
On the BC controller
side
P200 model or below
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
(Brazed connection)
ø9.52 [3/8"]
(Brazed connection)
P201 - P300
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
P301 - P350
ø28.58 [1-1/8"]
(Brazed connection)
ø12.7 [1/2"]
(Brazed connection)
P351 - P400
ø22.2 [7/8"]
(Brazed connection)
P401 - P450
ø15.88 [5/8"]
(Brazed connection)
A
B
Indoor
Indoor
Indoor
P50 model or below P63-P140 models P200-P250 models
*2
Junction pipe kit
(Model name:
CMY-R160-J)
(Optional accessory)
BC controller (sub)
To Main BC controller
Connection: Brazed connection
*1
Reducer
(Standard supplied parts)
Maximum of 3 units per port
Total capacity of P80 or below
(All units connected to the same port
must be in the same operating mode.)
3*
Indoor
Indoor
Indoor
Branch joint (Model name:CMY-Y102S-G2)
(Optional accessory)
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...