![Mitsubishi Electric PURY-(E)P200 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/mitsubishi-electric/pury-e-p200/pury-e-p200_service-handbook_1811251022.webp)
[
I
Read Before Servicing ]
- 13 -
HWE0713A
GB
[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical
property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a con-
fined area.
*1 When CFC11 is used as a reference
*2 When CO
2
is used as a reference
2. Refrigerant
composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To
be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn
out, the composition of the remaining refrigerant will change and become unsuitable for use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure
characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
New Refrigerant (HFC type)
Conventional Refriger-
ant (HCFC type)
R410A
R407C
R22
R32/R125
R32/R125/R134a
R22
Composition (wt%)
(50/50)
(23/25/52)
(100)
Type of Refrigerant
Pseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
Chloride
Not included
Not included
Included
Safety Class
A1/A1
A1/A1
A1
Molecular Weight
72.6
86.2
86.5
Boiling Point (°C/°F)
-51.4/-60.5
-43.6/-46.4
-40.8/-41.4
Steam Pressure
(25°C,MPa/77°F,psi) (gauge)
1.557/226
0.9177/133
0.94/136
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.0
42.5
44.4
Flammability
Nonflammable
Nonflammable
Nonflammable
Ozone Depletion Coefficient (ODP)
*1
0
0
0.055
Global Warming Coefficient (GWP)
*2
1730
1530
1700
Refrigerant Charging Method
Refrigerant charging in
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
Replenishment of Refrigerant after a Refrigerant
Leak
Available
Available
Available
Temperature (°C/°F)
Pressure (gauge)
R410A
R407C
R22
MPa/psi
MPa/psi
MPa/psi
-20/-4
0.30/44
0.18/26
0.14/20
0/32
0.70/102
0.47/68
0.40/58
20/68
1.34/194
0.94/136
0.81/117
40/104
2.31/335
1.44/209
1.44/209
60/140
3.73/541
2.44/354
2.33/338
65/149
4.17/605
2.75/399
2.60/377
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...