VI
Refrigerant Circuit ]
- 105 -
HWE0713A
GB
Thermis-
tor
TH3
(Pipe
temperature)
Controls defrosting during heating
operation
Degrees Celsius
0°C[32°F] :15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
Resistance
check
TH7
(Outdoor tem-
perature)
1) Detects outdoor air tempera-
ture
2) Controls fan operation
TH5
Fan operated on the 63LS and
TH5 values.
TH6
Controls defrosting during heating
operation
THHS
Inverter
heat sink tem-
perature
Controls inverter cooling fan
based on THHS temperature
Degrees Celsius
0°C[32°F] :161kohm
10°C[50°F] :97kohm
20°C[68°F] :60kohm
25°C[77°F] :48kohm
30°C[86°F] :39kohm
40°C[104°F] :25kohm
THBOX
Control box in-
ternal tempera-
ture detection
Sole-
noid
valve
SV1a
Discharge-suc-
tion
bypass
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
Continuity
check with a
tester
SV2
SV4a - SV4d
Heat
exchanger
capacity control
Controls outdoor unit heat ex-
changer capacity
SV5b
Heat
exchanger
capacity control
Prevents high-pressure-rise
Controls defrost cycle
AC220 - 240V
Closed while being powered/
open while not being powered
SV5c
Allows the refrigerant to pass
through the bypass pipe to pre-
vent an accumulation of liquid re-
frigerant
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
SV9
High-pressure-rise prevention
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
Heater
CH11
Heats the refrigerant in the com-
pressor
Cord heater
P250, EP200 models
1143 ohm 35W
P300 - 400, EP250 - EP300
models
889 ohm 45W
Resistance
check
4-way
valve
21S4a
Changeover between heating and
cooling
AC220-240V
Dead: cooling cycle
Live: heating cycle
Continuity
check with a
tester
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
R = 17k
50
R = 4016
R = 17
25/120
t
4016 273 t
1
323
1
exp
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...