VII
Control ]
- 11
6
-
HWE0713A
GB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed
A setting of CN3D is required.(page 23)
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SW3
1
Test run mode: en-
abled/disabled
SW3-2 disabled
SW3-2 enabled
Anytime after power on
A
-
2
Test run mode: ON/
OFF
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
A
-
3
Defrost start temper-
ature
<P2
5
0 - P300>
<EP200>
-10°C [14°F]
-5°C [23°F]
Anytime after power on
B
B
<P350 - P400>
<EP250 - EP300>
-8°C [18°F]
4
Defrost end temper-
ature
<P2
5
0 - P300>
<EP200>
10°C [50°F]
<P2
5
0 - P300>
<EP200>
15°C [59°F]
Anytime after power on
(except during defrost op-
eration)
B
B
<P350 - P400>
<EP250 - EP300>
7°C [45°F]
<P350 - P400>
<EP250 - EP300>
12°C [54°F]
5
-
-
-
-
-
-
6
-
-
-
-
-
-
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
Model setting
Outdoor standard
static pressure
Outdoor high static
pressure
Before being energized
C
C
10
Model setting
High static pressure
60Pa
High static pressure
30Pa
Before being energized
C
C
SW4
1
-
-
-
-
-
-
2
-
-
-
-
-
-
3
Refrigerant amount
adjustment
Normal operation
mode
Refrigerant amount
adjust mode
Anytime after being ener-
gized (except during ini-
tial startup mode.
Automatically cancelled
90 minutes after com-
pressor startup)
A
-
4
Low-noise mode/
step demand switch-
ing
Low-noise mode
(Note 3)
Step demand mode Before being energized
C
C
5
-
-
-
-
-
-
6
Cumulative com-
pressor operation
time data deletion
Cumulative com-
pressor operation
time data is re-
tained.
Cumulative com-
pressor operation
time data is delet-
ed.
Anytime after power on
(when the unit is turned
on)
C
C
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
-
-
-
-
-
-
10
-
-
-
-
-
-
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...