IX
Troubleshooting ]
- 21
3
-
HWE0713A
GB
1. Error
Code
Heatsink temperature sensor (THHS) fault (Detail code 01)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 283)
1. Error
Code
Liquid inlet temperature sensor (TH11) fault (BC controller)
Bypass outlet temperature sensor (TH12) fault (BC controller)
LEV3 outlet temperature sensor (TH15) fault (BC controller)
LEV3 inlet temperature sensor (TH16) fault (BC controller)
2. Error definition and error detection method
If a shorted (high temperature intake) or open (low temperature intake) thermistor (TH11, TH12, TH15, or TH16) is detected
during operation, the unit makes an error stop, and an error code "5111," "5112," "5115," or "5116" appears on the display.
Detection of a short- or open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the
operation mode is changed.
3. Cause, check method and remedy
<Reference>
5110
Cause
Check method and remedy
(1)
INV board failure
If the problem recurs when the unit is put into operation, replace the INV board.
5111
5112
5115
5116
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
(6)
Thermistor input circuit failure on the control
board
Check the intake temperature of the sensor with the LED monitor.
When the temperature is far different from the actual temperature,
replace the control board.
TH11
TH12
TH15
TH16
Open detection
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
Short detection
110 C [230 F ] and above (0.4 k )
110 C [230 F ] and above (0.4 k )
70 C [158 F ] and above (0.4 k )
110 C [230 F ] and above (0.4 k )
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...