[
II
Restrictions ]
35
- 35 -
HWE0713A
GB
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block for indoor-
outdoor transmission line (TB3) on the outdoor units (OC and OS),
of the terminal block for indoor-outdoor transmission line (TB02) on
the main and sub BC controllers (BC and BS), of the terminal block
for indoor-outdoor transmission line (TB5) on each indoor unit (IC),
and the S terminal of the system controller.(Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically
designated as OC and OS in the order of capacity from large to small
(if two or more units have the same capacity, in the order of address
from small to large).
Shielded cable connection
Daisy-chain the ground terminal (
) on the outdoor units (OC and
OS), the S terminal of the terminal block (TB02) on the BC and BS,
and the S terminal of the terminal block (TB5) on the indoor unit (IC)
with the shield of the shielded cable.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block for transmis-
sion line for centralized control (TB7) on the outdoor units (OC) in
different refrigerant circuits and on the OC and OS in the same re-
frigerant circuit.
If a power supply unit is not connected to the transmission line for
centralized control, replace the power jumper connector on the con-
trol board from CN41 to CN40 on only one of the outdoor units.
Set the central control switch (SW2-1) on the control board of all out-
door units to "ON."
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the out-
door units (OC, OS) with the shield wire of the shielded cable. Short-
circuit the earth terminal (
) and the S terminal on the terminal
block (TB7) on the outdoor unit whose power jumper connector is
mated with CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5) on the in-
door units (IC) to the appropriate terminals on the terminal block for
indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po-
larized two-wire)
Indoor units must be interlocked with the LOSSNAY unit using the
system controller. (Refer to the operation manual for the system
controller for the setting method.) Interlock setting from the remote
controller is required if the ON/OFF remote controller alone is con-
nected.
5) Switch setting
Address setting is required as follows.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
Proce-
dures
Unit or controller
Ad-
dress
setting
range
Setting method
Notes
Fac-
tory
set-
ting
1
Indoor
unit
Main unit
IC
01 to
50
Assign the smallest address to the main unit
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the fol-
lowing order.
(i) Indoor unit to be connected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2
Make the settings for the indoor units in the
way that the formula "(i) < (ii) < (iii)" is true.
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
00
Sub unit
Assign sequential numbers starting with the
address of the main unit in the same group
+1. (Main unit a1, main unit address
+2, main unit a3, etc.)
2
LOSSNAY
LC
01 to
50
Assign an arbitrary but unique address to
each of these units after assigning an address
to all indoor units.
None of these addresses may
overlap any of the indoor unit
addresses.
00
3
MA
remote
controller
Main
remote con-
troller
MA
No set-
tings re-
quired.
-
Make the same indoor unit
group settings with the system
controller as the ones that
were made with the MA remote
controller.
Main
Sub
remote con-
troller
MA
Sub
remote
controller
Settings to be made with the Sub/
Main switch
4
Outdoor unit
OC
OS
51 to 100
Assign sequential address to the outdoor
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con-
troller overlaps any of the
addresses that are assigned
to the outdoor units or to the
sub BC controller, use a dif-
ferent, unused address with-
in the setting range.
The use of a sub BC control-
ler requires the connection
of a main BC controller.
00
5
Auxiliary
outdoor
unit
BCcon-
troller (Sub)
BS
51 to 100
Assign an address that equals the sum of the
smallest address of the indoor units that are
connected to the sub BC controller and 50.
BC control-
ler (Main)
BC
OC (or OS if it exists) +1
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...