1. Error
Code
High pressure fault 1 (Outdoor unit)
2. Error definition and error detection method
1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out-
door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 min-
utes after the first stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts
after 3 minutes automatically.
3) If the pressure of 3.87MPa [561psi] or higher is detected by the pressure sensor (the third detection) within 30 minutes of the
second stop of the outdoor unit, the outdoor unit will make an error stop, and the error code "1302" will be displayed.
4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection
is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects
4.15
+0,-0.15
MPa [601
+0,-22
psi]
3. Cause, check method and remedy
1302
Cause
Check method and remedy
(1)
Indoor unit LEV actuation failure
Perform a heating operation and check the op-
eration.
Cooling: LEV on the indoor unit
LEV1,2,3
SVM1,1b,2,2b
SVA
Heating: LEV on the indoor unit
LEV3
SVM2,2b
SVB,SV4a - 4d
Refer to the page on troubleshooting for LEV
and solenoid valve.(page 269)
(2)
BC controller LEV malfunction Heating only or heating main :
Indoor LEV 3
Defrost : LEV3
(3)
BC controller SVM1 and 2 malfunction
->Cooling only or defrost
(4)
BC controller SVA and SVC malfunction
->Cooling only or cooling main
(5)
BC controller SVB malfunction ->Heating only or heating main
Solenoid valve SV malfunction(4a-4c (P2
5
0-P300, EP200
models) ,4a-4d(P350-P400, EP250-EP300 models)) ->Cooling
only or cooling main
(6)
Port address setting error.
Confirm the port address of the indoor unit.
(7)
Refrigerant service valve actuation failure
Confirm that the refrigerant service valve is fully
(8)
Short cycle on the indoor unit side
Check the indoor units for problems and correct
them, if any.
(9)
Clogged filter on the indoor unit
(10)
Reduced air flow due to dirty fan on the indoor unit fan
(11)
Dirty heat exchanger of the indoor unit
(12)
Indoor fan (including fan parts) failure or motor failure
Items (7) through (12) above reduce the condensing capability
of the unit, resulting in high-pressure rise during heating oper-
ation.
(13)
Short cycle on the outdoor unit
Check the outdoor units for problems and cor-
rect them, if any.
(14)
Dirty heat exchanger of the outdoor unit
(15)
Outdoor fan (including fan parts) failure, motor failure, or fan
controller malfunction
Items (13) through (15) above reduce the condensing capabil-
ity of the unit, resulting in high-pressure rise during cooling op-
eration.
Check the fan on the outdoor unit.
Refer to the section on troubleshooting the out-
door unit fan.(page 269)
(16)
Solenoid valve (SV1a) malfunction
The by-pass valve (SV1a) can not control rise in high pressure.
Refer to the section on troubleshooting the sole-
noid valve.(page 266)
(17)
Thermistor failure (TH3, TH7)
Check the thermistor resistor.(page 216)
(18)
Pressure sensor failure
Refer to the page on the troubleshooting of the
high pressure sensor. (page 264)
(19)
Failure of the thermistor input circuit and pressure sensor input
circuit on the controller board
Check the sensor temperature/pressure on the
LED monitor.
(20)
Thermistor mounting problem (TH3, TH7)
Check the sensor temperature/pressure on the
LED monitor.
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...