IX
Troubleshooting ]
- 29
3
-
HWE0713A
GB
NO.
Parts to be serviced
1 Solenoid
valve
block
ASSY
(SV4a, SV4b, SV4d)
2 Check
valve
(CV4a)
3 Check
valve
(CV6a, CV8a, CV9a, CV10a)
1. Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement instruc-
tions
* Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b,
SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures.
1. Applicable models
• PURY-
P
250, 300YHM-A (-BS)
•
PURY-EP200YHM-A
(-BS)
2. Parts to be serviced, Set-content
Following instructions are applicable to 1-3 service parts on the table below.
Things required for replacing
Item
Solenoid valve block service parts set
[Set-content]
•
Replacement
instructions
• Solenoid valve block ASSY
•
Connecting
pipe
(
φ
9.52 [3/8"])
Service parts replacement instructions set
[Set-content]
•
Replacement
instructions
•
Connecting
pipe
(
φ
9.52 [3/8"])
Numbers
1
1
1
1
1
1
1
3. Procedures
*
Precautions for starting replacement
•
Check that the main power supply is OFF.
•
Check that no refrigerant is in the outdoor unit.
Remove each part according to the 1)-3) procedures on the next page before replacing service parts.
Mount the removed parts back in place in a reversed procedures of 1)-3) on the next page after replacing service
parts.
(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement procedures
●
To remove Solenoid valve block ASSY
①
Remove the solenoid valve block coil cover, solenoid valve coil, and peripheral cables.
②
Remove the screw (M5) that fixes the solenoid valve block and the supporting plate for solenoid valve block.
③
Cut the pipe at the position indicated on the next page with a pipe cutter. Remove the pipe from the brazed A part.
④
Debraze B-G parts (total 6 places).
⑤
Do not damage heat exchanger fins and peripheral piping devices when removing the Solenoid valve block ASSY.
●
To install Solenoid valve block ASSY
⑥
Mount the Solenoid valve block ASSY replacement to the unit with care not to damage heat exchanger fins and
peripheral piping devices.
Fix the Solenoid valve block ASSY and the supporting plate with the fixing screw (M5).
⑦
Braze B-G part (total 6 places), and connect the solenoid valve block and the heat exchanger header with the connect-
ing pipe (
φ
9.52 [3/8"]) that comes with the service parts set.
⑧
Mount the solenoid valve block coil cover, solenoid valve coil, and peripheral cables back in place.
*
Precautions for replacing Solenoid valve block ASSY
•
Be sure to perform no-oxidation brazing when brazing.
•
After brazing, check the condition around the brazing. After confirming no leakage, evacuate the air
inside. (*1)
•
Perform brazing with care of the flame direction so that it does not burn cables and plates etc. in the unit.
•
Remove the brazing part protecting heat exchanger fins from burning, and replace the service parts.
*1: Refer to Chapter I [8] Vacuum Drying (Evacuation) for detailed procedure.
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...