VIII
Test Run Mode ]
- 17
2
-
HWE0713A
GB
Operation
Outdoor unit model
PURY-EP300YHM-A
Model name of BC controller
CMB-P104V-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C
[81°F/66°F]
Outdoor
35°C/-
[95°F/-]
Indoor unit
No. of connected units
Unit
3
No. of units in operation
3
Model
-
112/112/112
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
35 [82]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
20.4 [45]
Outdoor
unit
Electric current
A
13.3
Voltage
V
400
Compressor frequency
Hz
74
LEV open-
ing
Indoor unit
Pulse
325/325/325
BC controller (1/2/3)
2000/-/180
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.78/0.86
[403/125]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.59/2.59
[375/375]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
80 [176]
Heat exchanger outlet
(TH3)
38 [100]
Accumulator inlet
8 [46]
Accumulator outlet
8 [46]
Compressor inlet
19 [66]
Compressor shell bottom
42 [108]
Indoor unit
LEV inlet
19 [66]
Heat exchanger outlet
6 [43]
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...