VI
Refrigerant Circuit ]
- 111 -
HWE0713A
GB
(5) HB type
Part name
Symbols
(functions)
Part
code
Usage
Specifications
Check method
Thermistor TH12
(Bypass
outlet tem-
perature)
LEV control (Superheat)
0°C[32°F] : 15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
TH15
(Bypass in-
let tempera-
ture)
LEV control (Superheat)
Solenoid
valve
SV A
Provides refrigerant to indoor
unit in cooling operation
AC220-240V
Open while being powered/
closed while not being pow-
ered
Continuity
check with a
tester
SV B
Provides refrigerant to indoor
unit in heating operation
SV C
Provides refrigerant to indoor
unit in cooling operation
LEV
LEV3
Pressure differential control
DC12V
Opening of a valve driven by a
stepping motor
0-2000 pulses
Same as
indoor LEV
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
Содержание PURY-(E)P200
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 63: ... II Restrictions 54 HWE0713A GB ...
Страница 65: ... 56 ...
Страница 80: ... III Outdoor Unit Components 71 HWE0713A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 81: ... 72 III Outdoor Unit Components GB HWE0713A ...
Страница 83: ... 74 ...
Страница 91: ... 82 IV Remote Controller GB HWE0713A ...
Страница 93: ... 84 ...
Страница 104: ... 95 HWE0713A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 9 2 Principal Parts and Functions 10 ...
Страница 105: ... 96 ...
Страница 121: ... 112 VI Refrigerant Circuit GB HWE0713A ...
Страница 123: ... 114 ...
Страница 151: ... 142 ...
Страница 195: ... 186 ...
Страница 315: ... 306 IX Troubleshooting GB HWE0713A ...
Страница 316: ... 307 HWE0713A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 309 ...
Страница 317: ... 308 ...