- 26 -
[
II
Restrictions ]
3. System in which two MA remote controllers are connected to one indoor unit
Sample control wiring
Notes
Maximum allowable length
1.Leave the male connector on the female power supply
switch connector (CN41) on the outdoor unit as it is.
2.It is not necessary to provide grounding to S terminal on the
terminal block for transmission line for centralized control
(TB7).
3.Although two indoor controllers (controller circuit boards)
are equipped inside the indoor unit, the board on No.2 side
(lower side) is not used. Do not connect wiring to the lower
controller circuit board.
4.No more than two MA remote controllers (including both
main and sub controllers) can be connected to a group of in-
door units. If three or more MA remote controllers are con-
nected, remove the wire for the MA remote controller from
the terminal block (TB15).
(1) Indoor/outdoor transmission line
Same as [4] 1.
(2) MA remote controller wiring
Maximum overall line length (0.3 to 1.25mm
2
)
m1+m2 200m
NO
NO
*Two indoor controllers (controller circuit boards)
are equipped in the indoor unit (P500).
Leave the male
connector on
CN41 as it is.
OC
TB3
TB7
M1M2
M1M2S
51
IC
TB5-1
A1 B1 S
01
TB5-2
A2 B2 S
02
A B
TB15
1 2
MA(Main)
A B
MA(Sub)
L1
A1 B2
MA
m1
m2
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...