- 53 -
[
IV
Indoor Unit Components ]
[5] Separating the top and bottom of the unit
< Model 250 >
Filters (2)
Filter cover
Side panel: 14 screws
Front panel: 6 screws
Front panel:
2 chains
Rear panel: 9 screws
Side panel: 14 screws
Rear panel: 8 screws
A
(on four corners)
Filters (3)
Rear panel: 7 screws on each
Filter cover
Rear panel: 8 screws
Side panel: 14 screws
A
(on four corners)
Front panel:
2 hinges on each
Side panel:
14 screws
Bolt
Screw
Pull these pins up and down respectively
to remove the front panel.
Bolt
Screw
Detailed vie w of section A
< Model 500 >
Heat exchanger
unit (top)
Fan unit
(bottom)
Height (mm)
1120+510
*1
860
<Dimensions and weight of parts>
* Length of protruded pipe (removable)
Width (mm)
P250:1380
P500:1980
P250:1380
P500:1980
Depth (mm)
780
780
Weight (kg)
P250:158
P500:246
P250:128.5
P500:159
[Fig.1]
The top and the bottom of the unit can be separated. (Requires brazing)
When separating the top and the bottom of the unit, perform the work on a level surface.
Follow the procedures below when separating the sections.
Necessary tools and materials:
Ratchet wrench with a socket size of 17 mm (for M10)
General tools
Cable ties (for wires)
Gray vinyl tape (for pipes)
Supporting wood piece Height 800 mm x width 100 mm x thickness 20 (mm) 1 piece
(1) Removing the decoration panel and filter
<Model 250>
Remove the front panels (2), rear panels (2), and the side panels (2) in this order by removing the hinges and the screws on the unit as shown in [Fig.1].
Open the filter cover and remove the filters (2 filters).
<Model 500>
Remove the front panels (4), rear panels (3), and the side panels (2) in this order by removing the hinges and screws on the unit as shown in [Fig.1].
Open the filter cover and remove the filters (3 filters).
(2) Disconnecting the electric wires
Disconnect the wiring connectors from the remote controller, thermistor, float switch, lamp , and linear expansion valve as shown in [Fig.2].
After removing the connectors, pull out the wires from the control box.
Unclamp the wires from the frame.
Put all wires together in a bundle on the unit.
(3) Removing the drain hose and the pipes from the brazed section of the pipe
Remove the drain hose by unscrewing the screws on both ends of the hose band.
Peel off the pipe cover on the pipe so that the torch flame will not reach the cover. Remove the pipe from the brazed section as shown in [Fig.3].
*Protect the section around the area to be worked on from the torch flame (drain pan, wiring, insulation material on the frame etc).
1
2
(4) Separate the top and the bottom of the unit
Unscrew the screws and loosen bolt that are marked with the letter A in
Loosen bolt
[Fig.1] (on f our corners)
loose enough to allow the top and the bottom of the unit to be separated. Be sure to re-tighten bolt after sepa
and bottom (Tightening torque:
rating the top
74N.m).
Separation work is now complete. Exercise caution not to damage or scratch the unit during transportation or get your fingers caught between the units.
1
2
2
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...