- 11 -
[
I
Read Before Servicing ]
[9] Refrigerant Charging
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C, R125=-49°C) and can almost be handled the same
way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and
become unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down.
Check the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in
the liquid state.)
Refer to "9. (5) Refrigerant leak".
Cylinder with a siphon
Cylinder color R410A is pink.
Refrigerant charging in the liquid state
Cylin-
der
liquid
Valve
Valve
liquid
Cylin-
der
Cylinder without a siphon
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...