- 76 -
[
VII
Control ]
SW4
1
-
-
-
-
2
-
-
-
-
3
-
-
-
-
4
Reset of the integrat-
ed operation time Val-
id/Invalid
(comp 1 side)
Disabled
Enabled
Anytime after power on
5
Reset of the integrat-
ed operation time Val-
id/Invalid
(comp 2 side)
Disabled
Enabled
Anytime after power on
6
-
-
-
-
7
-
-
-
-
8
-
-
-
-
9
-
-
-
-
10
Dehumidification pri-
ority control Valid/In-
valid
Enabled
Disabled
Anytime after power on
SW5
1
-
-
-
-
2
Rotation time under
two-refrigerant circuit
system
240hr
120hr
Anytime after power on
3
-
-
-
-
4
Thermo-ON/OFF
conditions control
Valid
Invalid
Anytime after power on
5
-
-
-
-
6
-
-
-
-
7
-
-
-
-
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
SWU
3
Reset of the integrat-
ed operation time
Resetting the integrated operation
time according to the settings of SW4-
4 and 4-5
After power on. (when switching from
0 or 1 to 2)
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
OFF
ON
Note: All are set to OFF at factory shipment. (* For PUY series, only the SW4-9 is set to ON.)
Unless otherwise specified, set the switch to OFF where indicated by "-," which may be set to a certain setting
for a reason.
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...