- 167 -
[
IX
Troubleshooting ]
[5] Refrigerant Leak
1. Leak spot: In the case of extension pipe for indoor unit
1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side.
2) Stop all the indoor units, and close the liquid ball valve (BV2) inside the outdoor unit while the compressor is being
stopped.
3) Stop all the indoor units; turn on SW3-6 on the outdoor unit main board while the compressor is being
stopped.(Pump down mode will start, and all the indoor units will run in cooling test run mode.)
4) In the pump down mode (SW3-6 is ON), all the indoor units will automatically stop when the low pressure (LPS)
reaches 0.382MPa or less or 15 minutes have passed after the pump mode started. Stop all the indoor units and
compressors when the pressure indicated by the pressure gauge, which is on the check joint (CJ2) for low-pressure
service, reaches 0.284MPa or 20 minutes pass after the pump down operation is started.
5) Close the gas ball valve (BV1) inside the outdoor unit.
6) Collect the refrigerant that remains in the extended pipe for the indoor unit. Do not discharge refrigerant into the
atmosphere when it is collected.
7) Repair the leak.
8) After repairing the leak, vacuum the extension pipe and the indoor unit.
9) To adjust refrigerant amount and to check the composition of refrigerant, open the ball valves (BV1 and BV2) inside
the outdoor unit and turn off SW3-6.
2. Leak spot: In the case of outdoor unit
1) Run all the indoor units in the cooling test run mode.
(i) To run the indoor unit in test run mode, turn SW3-2 from OFF to ON when SW3-1 on the outdoor MAIN board
is ON.
(ii) Change the setting of the remote controller for all the indoor units to the cooling mode.
(iii) Check that all the indoor units are performing a cooling operation.
2) Check the values of Tc and TH7.
(To display the values on the LED screen, use the self-diagnosis switch (SW1) on the outdoor unit main board.)
(i) When Tc-TH7 is 10K or more : See the next item 3).
(ii) When Tc-TH7 is less than 10K : After the compressor stops, collect the refrigerant inside the system, repair
the leak, perform evacuation, and recharge new refrigerant. (Leak spot: In the case of outdoor unit, handle in
the same way as heating season.)
3) Stop all the indoor units, and stop the compressor.
(i) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor MAIN
board is ON.
(ii) Check that all the indoor units are being stopped.
4) Close the ball valves (BV1 and BV2).
5) To prevent the liquid seal, extract small amount of refrigerant from the check joint of the liquid ball valve (BV2), as
the liquid seal may cause a malfunction of the unit.
6) Collect the refrigerant that remains inside the outdoor unit.Do not discharge refrigerant into air into the atmosphere
when it is collected.
7) Repair the leak.
8) After repairing the leak, replace the dryer with the new one, and perform evacuation inside the outdoor unit.
9) To adjust refrigerant amount, open the ball valves (BV1 and BV2) inside the outdoor unit.
Note : When the power to the outdoor/indoor unit must be turned off to repair the leak after closing the ball valves
specified in the item 4, turn the power off in approximately one hour after the outdoor/indoor units stop.
(i) When 30 minutes have passed after the item 4 above, the indoor unit lev turns from fully closed to slightly open
to prevent the refrigerant seal.
(ii) Therefore, if the power source is turned off within 30 minutes, the lev remains fully closed and the refrigerant
remains sealed.
When only the power for the indoor unit is turned off, the indoor unit LEV turns from faintly open to fully closed.
Tc self-diagnosis switch
TH7 self-diagnosis switch
1 2 3 4 5 6
7 8 9 10
ON
1 2 3 4 5 6
7 8 9 10
ON
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...