- 6 -
[
I
Read Before Servicing ]
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use
pipes that meet the local standards.
Flare processing dimensions (mm[in])
Pipe size (mm[in])
A dimension (mm)
R410A
R22, R407C
ø6.35
[1/4"]
9.1
9.0
ø9.52
[3/8"]
13.2
13.0
ø12.7
[1/2"]
16.6
16.2
ø15.88
[5/8"]
19.7
19.4
ø19.05
[3/4"]
24.0
23.3
Flare nut dimensions (mm[in])
Pipe size (mm[in])
B dimension (mm)
R410A
R22, R407C
ø6.35
[1/4"]
17.0
17.0
ø9.52
[3/8"]
22.0
22.0
ø12.7
[1/2"]
26.0
24.0
ø15.88
[5/8"]
29.0
27.0
ø19.05
[3/4"]
36.0
36.0
Dimension A
Dimension B
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...