- 136 -
[
IX
Troubleshooting ]
7110
The indoor unit cannot be
operated as the connec-
tion between indoor units
in the system is not nor-
mal.
(1) Shutdown of the power of
the power supply exten-
sion unit for transmission
line
(2) Power reset of the power
supply extension unit for
transmission line and of
the outdoor unit
Check that the power supply of the
power supply extension unit for
transmission line is connected to the
switch of the indoor unit, and that the
power is not shutdown.
(The unit does not operate normally
if the power supply of the power sup-
ply extension unit for transmission
line is not turned on.
-> Reset the power of the outdoor
unit.)
7111
Indoor unit
OA processing
unit
Remote controller sen-
sor failure
This error occurs when
the temperature data is
not sent although the re-
mote controller sensor is
specified.
The remote controller without
the temperature sensor (the
wireless remote controller or
the M-NET compact remote
controller (mounted type)) is
used and the remote controller
sensor for the indoor unit is
specified. (SW1-1 is ON.)
Replace the remote controller with
the one with built-in temperature
sensor.
7113
Outdoor unit
Model setting error
Function setting error
due to resistance
(1) Faulty wiring
(2) Disconnected connector,
short-circuit, or contact
failure
(3) The type of the INV circuit
board is not applicable to
the compressor.(Replaced
wrongly)
(4) Wrong setting of the main
circuit board of the system
unit
1) Check the connector on the
main circuit board and the con-
nectors of CNTYP 1, 4, and 5.
2) Check the type of the replaced
INV circuit board. If it is not appli-
cable to the compressor, replace
the board.
3) Check that the DipSW5-8 on the
main circuit board of the system
unit is OFF. If it is ON, turn it
OFF.
7116
Outdoor unit
Replace Multi setting
error
The refrigerant pipe has
not been washed.
Wrong settings are made on
the function selection switch
(SW4-3).
"Replace" is set.
Check that the SW4-3 on the main
circuit board is OFF.
7117
Outdoor unit
Model setting error
(1) Faulty wiring
(2) Disconnected connector,
short-circuit, or contact
failure
Check for the contact of the connec-
tor CNTYP1, 4, 5 on the main board.
7130
Outdoor unit
Indoor unit
Incompatible units
(1) The indoor unit that uses
R22 or R407C refrigerant
is connected
(2) The wrong unit model is
connected.
(3) The ROM on the outdoor
unit has not been rewrit-
ten. (The ROM on the out-
door unit to be connected
to the PFD-type indoor unit
must be written.)
1) Check the connected indoor unit
model.
2) Check the S/W version.
Error
Code
Error source
Error definition and error
detection method
Cause
Check method and remedy
Содержание PU(H)Y-P250YGM-A
Страница 1: ...Models Service Handbook AIR CONDITIONERS PU H Y P250YGM A PUHY P500YGM A PFD P250VM E PFD P500VM E ...
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 41: ... 32 ...
Страница 53: ... 44 ...
Страница 67: ... 58 ...
Страница 72: ... 63 VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 65 2 Principal Parts and Functions 68 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 105: ... 96 ...
Страница 107: ... 98 ...
Страница 117: ... 108 ...
Страница 119: ... 110 ...
Страница 182: ... 173 X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 175 ...
Страница 183: ... 174 ...