![Mitsubishi Electric NZ2GF-CCB Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/mitsubishi-electric/nz2gf-ccb/nz2gf-ccb_user-manual_1811813033.webp)
31
CHAPTER 3 SPECIFICATIONS
3
3.
8
List
of
Rem
o
te
Buf
fe
r M
e
mor
y A
reas
3.8
List of Remote Buffer Memory Areas
This section lists the remote buffer memory areas of the bridge module. The data in the remote buffer memory is read
and written with the REMFR and REMTO instructions of a program. For the REMFR and REMTO instructions, refer to
the user's manual for the master/local module used.
When the power supply of the module is turned off then on or reset, the data in the remote buffer memory returns to
the default (initial value).
*1
Shows whether the data can be read or written from/to the program.
R: Readable
W: Writable
Address
Name
Description
Read/Write
Reference
Decimal
Hexadecimal
0 to 127
0 to 7F
H
CC-Link parameter
information area
Stores the information (parameter) on the
bridge module to perform the data link with
the CC-Link remote I/O station and remote
device station.
R
128 to 223
80
H
to DF
H
System area
224 to 351
E0
H
to 15F
H
CC-Link remote input
(RX)
Stores the input status from the CC-Link
remote station.
R
352 to 479
160
H
to 1DF
H
CC-Link remote output
(RY)
Stores the output status of the CC-Link
remote station.
W
480 to 735
1E0
H
to 2DF
H
CC-Link remote
register (RWw)
Stores the transmitted data to the CC-Link
remote station.
W
736 to 991
2E0
H
to 3DF
H
CC-Link remote
register (RWr)
Stores the received data from the CC-Link
remote station.
R
992 to 1503
3E0
H
to 5DF
H
System area
1504 to 1535
5E0
H
to 5FF
H
CC-Link link special
relay
Stores the status of the data link of CC-Link. R/W (only the
first 32 points
can be
written)
1536 to 2047
600
H
to 7FF
H
CC-Link link special
register
Stores the status of the data link of CC-Link.
2048 to 32767
800
H
to 7FFF
H
System area
32768 to 33023
8000
H
to 80FF
H
Module monitor/control
area
Stores the remote READY, an error code,
and a warning code of the bridge module.
The areas are also used for a error clear
request.
R/W
33024 to 35327
8100
H
to 89FF
H
System area
Содержание NZ2GF-CCB
Страница 1: ...CC Link IE Field Network CC Link Bridge Module User s Manual NZ2GF CCB ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 35: ...33 CHAPTER 4 THE PROCEDURE BEFORE OPERATION 4 Memo ...
Страница 143: ...141 APPENDICES A Appendix 7 External Dimensions Appendix 7 External Dimensions 160 65 4 5 68 9 2 Unit mm ...
Страница 145: ...I 4 4 7 8 143 Memo ...
Страница 149: ......