117
APPENDICES
A
Appendix
2 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
(7) CC-Link link special register (address: 600
H
to 7FF
H
)
The CC-Link operating status can be checked with word information.
600
H
to 61F
H
are stored by the program and 620
H
to 7FF
H
are stored automatically.
Address
Name
Description
603
H
Multiple temporary
error invalid station
specification
Select whether to specify multiple temporary error invalid stations.
00: Multiple stations set in Temporary error invalid station specification (address: 604
H
to 607
H
) specified
01 to 64: A single station specified from 1 to 64 (The number represents the station number to be set as
a temporary error invalid station.)
604
H
605
H
606
H
607
H
Temporary error
invalid station
specification
Specify a temporary error invalid station.
0: Temporary error invalid station not specified
1: Temporary error invalid station specified
The stations need not be set by the number of occupied stations.
Error invalid stations, reserved stations, station with the last station number, and stations later than that
are excepted.
608
H
Line test station
setting
Set a station number where the line test is executed.
00: Entire system (executed to all stations)
01 to 64: Target station number
641
H
Data link restart
result
Whether the data link restart instruction using Data link restart (address: 5E0
H
.b0) has been normally
completed is stored.
0: Normal completion
Values other than 0: Error code (
645
H
Data link stop
result
Whether the data link stop instruction using Data link stop (address: 5E0
H
.b2) has been normally
completed is stored.
0: Normal completion
Values other than 0: Error code (
649
H
Temporary error
invalid station
specification result
Whether the temporary error invalid station specification has been normally completed is stored.
0: Normal completion
Values other than 0: Error code (
64B
H
Temporary error
invalid station
specification
cancel result
Whether the temporary error invalid station setting has been normally canceled is stored.
0: Normal completion
Values other than 0: Error code (
64D
H
Line test result
The result of a line test is stored.
0: Normal completion
Values other than 0: Error code (
64F
H
Parameter
information read
request result
The result of a parameter information read request is stored.
0: Normal
Values other than 0: Error code (
652
H
Automatic CC-Link
startup execution
result
The result of system configuration check when a station has been added to a system and the system
has started using the automatic CC-Link startup is stored.
0: Normal
Values other than 0: Error code (
to
to
to
to
to
The numbers 1 to 64 in the table are station numbers.
b15
16
32
48
64
15
31
47
63
14
30
46
62
13
29
45
61
4
20
36
52
3
19
35
51
2
18
34
50
1
17
33
49
b14
b13
b12
b3
b2
b1
b0
604
H
605
H
606
H
607
H
Содержание NZ2GF-CCB
Страница 1: ...CC Link IE Field Network CC Link Bridge Module User s Manual NZ2GF CCB ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 35: ...33 CHAPTER 4 THE PROCEDURE BEFORE OPERATION 4 Memo ...
Страница 143: ...141 APPENDICES A Appendix 7 External Dimensions Appendix 7 External Dimensions 160 65 4 5 68 9 2 Unit mm ...
Страница 145: ...I 4 4 7 8 143 Memo ...
Страница 149: ......