84
(2) Warning codes
Error code
(hexadecimal)
Classification
Error
description
Action
0201
H
Minor error
Data read error
(error history)
• The error is automatically corrected immediately after it has occurred.
However, the history of errors that have occurred before this error is lost.
• Take noise reduction measures such as using a shielded cable for
connection.
• If the same error occurs again, the module may be in failure. Please consult
your local Mitsubishi representative.
0203
H
Station number
switch changing
error
Reset the switch to the station number that was set when the module was
powered on.
0204
H
Momentary power
failure occurrence
Check the power supply to the bridge module.
0205
H
Startup mode
switch out of range
Set the startup mode switch to PRM.
0601
H
Invalid parameter
Write the parameters again using the parameter processing of slave station.
If the same error occurs, register the latest profile of the bridge module to the
engineering tool and write the parameters again.
If the same error occurs again, the hardware of the bridge module is in failure.
Please consult your local Mitsubishi representative.
0602
H
0603
H
0604
H
0605
H
0606
H
0607
H
Station information
setting error
In parameter processing of slave station, set "Station information" so that it
meets the following condition:
(16
A)+(54
B)
2304
• A: Number of remote I/O stations
• B: Number of remote device stations
0608
H
Remote device
station setting error
In parameter processing of slave station, set the parameters so that the
number of stations in which "Station type" of "Station information" is set to the
remote device station is 42 or less.
0609
H
Invalid station
specification error
In parameter processing of slave station, specify only the station numbers set
in "Station number" of "Station information" as the error invalid stations.
060A
H
Station number
setting error
In parameter processing of slave station, set the parameters so that the sum
of the number set in "Station number" and "Number of occupied stations" of
"Station information" is 64 or less.
060B
H
Invalid parameter
Write the parameters again using the parameter processing of slave station.
If the same error occurs, register the latest profile of the bridge module to the
engineering tool and write the parameters again.
If the same error occurs again, the hardware of the bridge module is in failure.
Please consult your local Mitsubishi representative.
060C
H
Reserved station
specification error
• In parameter processing of slave station, specify only the station numbers
set in "Station number" of "Station information" as the reserved stations.
• In parameter processing of slave station, check if all the station numbers
set in "Station number" of "Station information" are set as the reserved
stations.
060D
H
Station number
already in use error
In parameter processing of slave station, set the parameters so that there is
no duplication in "Station number" of "Station information".
060E
H
No parameter input
error
In parameter processing of slave station, any of "Total module connected",
"Retry count", "Automatic reconnection station count", or "Station information"
has not yet been written. Write the parameters.
Содержание NZ2GF-CCB
Страница 1: ...CC Link IE Field Network CC Link Bridge Module User s Manual NZ2GF CCB ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 35: ...33 CHAPTER 4 THE PROCEDURE BEFORE OPERATION 4 Memo ...
Страница 143: ...141 APPENDICES A Appendix 7 External Dimensions Appendix 7 External Dimensions 160 65 4 5 68 9 2 Unit mm ...
Страница 145: ...I 4 4 7 8 143 Memo ...
Страница 149: ......