104
(b) Remote READY (RWr0.b11)
This signal is used as an interlock condition when the master station reads/writes data.
After the bridge module is turned on, Remote READY (RWr0.b11) turns on.
If a moderate or major error (excluding a watchdog timer error) occurs, Remote READY (RWr0.b11) turns off.
(c) Warning status flag (RWr0.b12)
If a minor error occurs, Warning status flag (RWr0.b12) turns on.
When the cause of the error is removed, Warning code (RWr2) becomes 0 and Warning status flag (RWr0.b12)
turns off.
(2) Error code (RWr1)
In Error code (RWr1), information in Error code (address: 8001
H
) of the module monitor/control area is stored.
(
Page 83, Section 9.5)
(3) Warning code (RWr2)
In Warning code (RWr2), information in Warning code (address: 8002
H
) of the module monitor/control area is
stored. (
Page 83, Section 9.5)
0000
H
0000
H
OFF
ON
OFF
ON
Warning status flag
(RWr0.b12)
Remote READY
(RWr0.b11)
Warning code
(RWr2)
A minor error
has occurred.
The minor error
has been removed.
(Warning code)
Executed in the bridge module
Содержание NZ2GF-CCB
Страница 1: ...CC Link IE Field Network CC Link Bridge Module User s Manual NZ2GF CCB ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 35: ...33 CHAPTER 4 THE PROCEDURE BEFORE OPERATION 4 Memo ...
Страница 143: ...141 APPENDICES A Appendix 7 External Dimensions Appendix 7 External Dimensions 160 65 4 5 68 9 2 Unit mm ...
Страница 145: ...I 4 4 7 8 143 Memo ...
Страница 149: ......