124
(b) Error code (address: 8001
H
)
When a moderate or major error occurs (excluding a watchdog timer error), its error code is stored.
When Error clear request flag (address: 8080
H
.b10) is turned on after the cause of the error is removed, the
error code is cleared.
Errors that occurred in the past can be checked with the error history. (
The status of Error code (address: 8001
H
) is transferred to Error code (RWr1) of the remote register.
(c) Warning code (address: 8002
H
)
When a minor error occurs, its warning code is stored.
When the cause of the minor error is removed, Warning code (address: 8002
H
) is cleared.
Warnings that occurred in the past can be checked with the error history. (
The status of Warning code (address: 8002
H
) is transferred to Warning code (RWr2) of the remote register.