93
CHAPTER 9 TROUBLESHOOTING
9
9.
6
Check
ing t
he LE
Ds
(5) When the ERR. LED turns on or flashes
If the ERR. LED still turns on or flashes even after the above items have been checked, connect the engineering
tool to the master station. Then identify the cause of the error using the CC-Link IE Field Network diagnostics,
and take a corrective action. (
Page 78, Section 9.3)
(6) When the L ERR. LED turns on or flashes
Check item
Corrective action
Is the transmission speed/mode setting switch set
within the setting range?
Set the transmission speed/mode setting switch within the setting
range.
Are there multiple CC-Link master stations on the
same line?
Change the configuration so that only one CC-Link master station is
connected on one line.
Is the CC-Link cable normal?
• Check the cable for disconnection, short circuit, incorrect wiring,
poor contact, and usage not meeting the specifications
(transmission distance, station-to-station distance, coexistence of
different types of cables, and FG connection).
• Check if a transmission cable other than a CC-Link dedicated
cable is used.
• Check that a terminating resistor is connected.
Is there any noise affecting the system?
Check the wiring condition.
Is the same station number used for multiple CC-Link
stations?
Set a unique station number for each CC-Link remote station.
Check item
Corrective action
Is the CC-Link cable normal?
• Check the cable for disconnection, short circuit, incorrect wiring,
poor contact, and usage not meeting the specifications
(transmission distance, station-to-station distance, coexistence of
different types of cables, and FG connection).
• Check if a transmission cable other than a CC-Link dedicated
cable is used.
• Check that a terminating resistor is connected.
Is there any noise affecting the system?
Check the wiring condition.
Has the setting for the transmission speed/mode
setting switch been changed while the module is on?
After setting the transmission speed/mode setting switch, turn on
the module.
Содержание NZ2GF-CCB
Страница 1: ...CC Link IE Field Network CC Link Bridge Module User s Manual NZ2GF CCB ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 35: ...33 CHAPTER 4 THE PROCEDURE BEFORE OPERATION 4 Memo ...
Страница 143: ...141 APPENDICES A Appendix 7 External Dimensions Appendix 7 External Dimensions 160 65 4 5 68 9 2 Unit mm ...
Страница 145: ...I 4 4 7 8 143 Memo ...
Страница 149: ......